Product Introduction: GE Fanuc IC670GBI102 Genius Bus Interface Module
Core Technical Specifications
- Brand: GE Fanuc
- Model Number: IC670GBI102
- Product Type: Genius Bus Interface Unit (BIU)
- Nominal Voltage: 115 VAC / 125 VDC
- Operating Voltage Range: 90-135 VAC / 105-150 VDC
- Input Frequency: 47 to 63 Hz
- Bus Transmission Speed: 38.4, 53.6, 76.8, or 153.6 Kbaud
- Supported I/O Modules: Up to 8 modules
- Data Exchange Capacity: 128 bytes of I/O data per host per scan
- Power Consumption: 48 VA max @115VAC; 24W max @125VDC
- Power Supply Output: 6.5 VDC ±5% for connected modules
- Inrush Current: 20 Amps peak for 3 milliseconds maximum
Environmental & Physical Specifications
- Operating Temperature: 0°C to 60°C (32°F to 140°F)
- Storage Temperature: -40°C to 85°C (-40°F to 185°F)
- Relative Humidity: 5% to 95%, non-condensing
- Mounting: DIN Rail or panel mount via dedicated terminal block
- Connectors: Includes a D-sub connector for monitor/terminal connection
- Pre-fabricated Cables: Compatible with IC660BLM506 (150 ohm) and IC660BLM508 (75 ohm)
- Terminating Resistors: Supports 75, 100, 120, or 150-ohm resistors
- Reliability: MTBF (Mean Time Between Failures) > 183,000 hours
- Certifications: CE marked and cULus listed
Key Features & Functions
- The module establishes a critical link between Field Control I/O and host controllers via the Genius bus.
- It enables advanced functions like fault reporting, analog scaling, and range selection.
- LED indicators provide clear status for power and "Bus Active" conditions.
- Comprehensive self-diagnostics run automatically during startup to check for errors.
- The design includes a metal grounding strip for enhanced safety and noise immunity.
- The unit supports hot insertion and removal for easy maintenance without system shutdown.
- Data memory supports 256-byte blocks for discrete, analog, and status information.
Installation & Wiring Guide
- Use the included terminal block for mounting on a standard DIN rail.
- For wiring, we recommend using 90°C rated copper conductor wire.
- Always connect the metal grounding strip to a proper earth ground.
- Terminate both ends of the Genius bus cable with the appropriate resistor (75 or 150 ohm).
- Ensure the ambient air temperature stays within the specified 0°C to 60°C range.
- The module's power supply has a holdup time of 20 milliseconds maximum.
Frequently Asked Questions (FAQ)
-
Q: What power sources can I use with this unit?
A: You can power the module using either an AC source (90-135V) or a DC source (105-150V). -
Q: How many I/O modules can I connect to one IC670GBI102?
A: A single IC670GBI102 Genius Bus Interface can communicate with up to eight I/O modules. -
Q: How quickly can you ship the module, and what are the logistics options?
A: We have inventory on hand and ship within 5 days via major express services like DHL, FedEx, or UPS. -
Q: What is your return policy for this product?
A: We support a 30-day return period for the IC670GBI102 from the date of receipt, subject to our terms and conditions.
For further technical details or pricing on the IC670GBI102 Genius Bus Interface, please contact our sales team.
Contact: Email sales@nex-auto.com or call +86 153 9242 9628 on WhatsApp.
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.