Allen-Bradley 1756-OC8 ControlLogix Digital Output Module
Core Technical Specifications
- Brand & Manufacturer: Allen Bradley
- Series: ControlLogix
- Model Number: 1756-OC8
- Module Type: DC Output Module
- Rated Voltage: 48 Volts DC Source
- Operating Voltage Range: 30-60 Volts DC
- Output Points: 8 Points (4 points per group)
- Max Current per Point: 2 Amps at 60°C
- Max Current per Module: 8 Amps at 60°C
Electrical & Performance Data
- Surge Current: 4 Amps for 10 ms per point (repeatable)
- On-State Voltage Drop: 2 VDC maximum at 2A
- Off-State Leakage: 1 mA maximum per point
- Output Delay: 1 ms (Off to On), 2 ms (On to Off)
- Minimum Load Current: 2 mA
- Backplane Power: 0.89 Watts
- Current Draw: 165 mA @ 5.1V, 2 mA @ 24V
Installation & Compatibility
- Required Terminal Block: 20-pin 1756-TBNH or 1756-TBSH (sold separately).
- Mounting: Install in any slot of a grounded ControlLogix chassis.
- Protection Note: Module is not fused; use a fused IFM (Input/Output Module) for output protection.
- Recommended Fuse: 5x20mm 4A quick-acting fuse (e.g., SOC MQ2-4A).
- Isolation Voltage: 50 Volts continuous.
Operational & System Features
- Communication Formats: Rack Optimization, Scheduled Output Data, Listen-Only modes.
- Fault State Configuration: Set per point to On, Off, or Hold Last State (default is Off).
- Power Dissipation: 4.9 Watts maximum at 60°C.
- Thermal Dissipation: 16.71 BTU/hour.
- Operating Temperature: Rated for up to 60°C (140°F).
Frequently Asked Questions (FAQ)
-
Q: What voltage does the 1756-OC8 module require?
A: The 1756-OC8 operates on a 30-60V DC supply, with a nominal rating of 48V DC. -
Q: How much current can I draw from a single output?
A: Each output point supports a maximum continuous current of 2 Amps at 60°C. -
Q: What terminal block do I need for this module?
A: You need a 20-pin removable terminal block, either the 1756-TBNH or the 1756-TBSH. -
Q: Is fuse protection included with the module?
A: No, the module is not internally fused. We recommend using an external fused IFM for protection. A 4A quick-acting fuse is suggested. -
Q: Do you have the 1756-OC8 in stock ready to ship?
A: Yes, we stock the 1756-OC8 and typically ship orders within 5 business days.
For more information or to purchase the 1756-OC8 module, contact our sales team today.
Contact Information Inquiries: sales@nex-auto.com , +86 153 9242 9628
Partner NexAuto Technology Limited : https://www.nex-auto.com/
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.