Honeywell FS-TSDI-1624C Safe Current-Limited Digital Input FTA
Core Technical Specifications
- Brand: Honeywell
- Model: FS-TSDI-1624C
- Category: Safe Digital Input FTA (Field Termination Assembly)
- Type Numbers: FS-TSDI-1624C, FC-TSDI-1624C
- Input Channels: 16 channels, organized in two groups of 8.
- Input Voltage: Rated for 24 V DC with a -15% to +30% range.
- Approvals: Certified to CE, TUV, UL, CSA, and FM standards.
- Dimensions: Compact size: 170 mm × 70 mm × 60 mm (L × W × H).
Electrical Input & Protection Features
- Input Current: Typically ≤ 15 mA per channel at 24 V DC.
- Igniting Current: Limited to < 100 mA per channel at maximum voltage.
- Fuse Protection: Each group of 8 channels has a 250 mA fuse on the common + line.
- Fuse Details: SOC SHV12 250 mA fuse, rated for 400 V AC/DC.
- Max Output per Fuse: Limited to 175 mA for safety compliance.
Mounting, Wiring & Physical Data
- Mounting: Universal snap-in design for DIN EN rails (TS32/TS35).
- Rail Length Used: Occupies 171 mm of rail space.
- Terminal Specifications: Screw terminals accept wires up to 2.5 mm² (AWG 14).
- Strip Length: Prepare wire ends to 7 mm (0.28 in).
- Torque: Tighten terminals to 0.5 Nm (0.37 ft-lb).
Safety Specifications for Hazardous Locations
- Compliance: Designed for Class I, Division 2 hazardous areas.
-
Field Circuit Limits (Non-Incendive):
- Max Closed Loop Resistance: 250 Ω
- Min Open Loop Resistance: 15 kΩ
-
HYDROGEN (Group A & B) Environment:
- Max Loop Inductance: 8 mH
- Max Loop Capacitance: 0.3 µF
-
NON-HYDROGEN (Group C & D) Environment:
- Max Loop Inductance: 22 mH
- Max Loop Capacitance: 7 µF
Frequently Asked Questions (FAQ)
-
Q: What does "current-limited" mean for this FTA?
A: It uses 250 mA fuses to limit current, preventing ignition in hazardous (Class I Div 2) locations. -
Q: What safety modules does this FTA connect to?
A: It is designed to connect to a redundant pair of SDI-1624 safe digital input modules. -
Q: What is the input voltage for the TSDI-1624C?
A: It is designed for standard 24 V DC field input signals. -
Q: Are the fuses user-replaceable?
A: Yes, the 5x20 mm 250 mA fuses are replaceable for maintenance. -
Q: What is your return policy?
A: We support 30-day returns for items in original condition.
For further technical details or specific application questions, please contact us. sales@nex-auto.com | +86 153 9242 9628
Partner: NexAuto Technology Limited
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.