6ES7422-1FH00-0AA0 SIMATIC S7-400 Output Module 2A 230V

In stock (15 units), ready to be shipped
  • Vendor:

    Siemens

  • Type:

    Digital Output Module

  • Country of Origin:

    SE

  • Dimensions:

    29*21*2.5cm

  • Weight:

    650 g

  • Tags: Digital output module

6ES7422-1FH00-0AA0 SIMATIC S7-400 Digital Output Module

  • Brand & Model: Siemens 6ES7422-1FH00-0AA0, part of the SIMATIC S7-400 series, SM 422 family.
  • Output Channels: 16 digital outputs, galvanically isolated in groups of 4 channels.
  • Load Voltage: Rated 120/230 V AC, permissible range 79 V to 264 V AC, frequency 47 Hz to 63 Hz.
  • Output Current: Rated 2 A per channel, surge current up to 50 A per cycle, minimum load 10 mA.
  • Protection: Group fuse 8 A, 250 V (fast-acting), short-circuit protection with 100 A shutdown current.
  • Power Loss: Typical 16 W; backplane bus current max 400 mA at 5 V DC.
  • Switching Frequency: Resistive load 10 Hz, inductive 0.5 Hz, lamp load 1 Hz.
  • Output Delay: 0 to 1 max 1 ms; 1 to 0 max 1 AC cycle (resistive load).
  • Diagnostics: LED indicators for internal fault (fuse blown) and external fault (missing load voltage).
  • Isolation: 1500 V AC tested; channels isolated from backplane bus and each other (group-wise).
  • Cable Length: Shielded up to 1000 m, unshielded up to 600 m.
  • Environmental: Operating temperature up to 60 °C with derating; total current per group 4 A at 40 °C (6 A with fan).
  • Dimensions: 25 mm width, 290 mm height, 210 mm depth; weight approx. 800 g.

Frequently Asked Questions (FAQ)

  • Q: Is the 6ES7422-1FH00-0AA0 a genuine Siemens module?
    A: Yes, we supply only 100% genuine, new original Siemens modules.
  • Q: Can I use this module with 110 V AC supply?
    A: Yes, the permissible range is 79–264 V AC, so 110 V AC works fine.
  • Q: What is the maximum switching frequency for inductive loads?
    A: For inductive loads, the max switching frequency is 0.5 Hz (according to IEC 60947-5-1 AC15).
  • Q: How do I know if a fuse is blown?
    A: The red INTF LED indicates internal fault (fuse blown); check and replace the 8 A fast fuse.
  • Q: Is the output short-circuit protected?
    A: Yes, each group has a fuse (8 A, 250 V) and requires a minimum 100 A shutdown current.
  • Q: What is the total current per group at 60 °C?
    A: At 60 °C, the max current is 2 A per group (or 5 A with fan assembly).
  • Q: Can I return this module if it doesn't fit my system?
    A: Yes, we support a 30-day return policy for unused items in original packaging.
  • Q: How long does delivery take?
    A: We ship within 5 days; transit time depends on your location (FedEx/UPS/DHL).

Contact Information: For inquiries, email sales@nex-auto.com or call +86 153 9242 9628 (WhatsApp). Partner: NexAuto Technology Limited

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most