Home
TC-FID161 Honeywell 16-Channel Digital Input DIN-Rail Module
1
/
of
3
TC-FID161 Honeywell 16-Channel Digital Input DIN-Rail Module
No reviews
In stock (15 units), ready to be shipped
-
Vendor:
Honeywell
-
Type:
Digital Input Module
-
Country of Origin:
USA
-
Dimensions:
7.5*9.5*4.5cm
- Weight:
300 g
- Tags: Digital input module
Honeywell TC-FID161 24 Vdc Sink Digital Input Module
Key Technical Specifications
- Brand & Model: Honeywell TC-FID161 – 16-channel sinking digital input module.
- Input Voltage Range: ON-state from 10 Vdc to 31.2 Vdc; OFF-state maximum 5.0 Vdc.
- Current Ratings: ON-state current 2 mA minimum, 8.8 mA nominal at 24 Vdc, 12.1 mA maximum. OFF-state current 1.5 mA minimum.
- Input Impedance: 2.5 kΩ ensures consistent signal loading across all channels.
- Selectable Filter Times: OFF-to-ON and ON-to-OFF from 256 µs up to 32 ms (default 256 µs).
- Dielectric Strength: 1900 Vdc for 1 second between user and system (channels non-isolated).
- Power & Thermal: Max Flexbus current 25 mA; power dissipation 6.1 W at 31.2 Vdc; thermal dissipation 20.8 BTU/hr.
- Environmental Limits: Operates 0 to 55 °C, stores -40 to 85 °C, 5–95% non-condensing RH.
- Shock & Vibration: 30g operating shock, 50g non-operating; 5g vibration per IEC 68-2-6.
- Wiring & Mounting: Accepts 12 AWG stranded wire (4 mm²), 90 °C insulation; terminal torque 4–7 in-lb.
- Indicators: 16 yellow LED status indicators for individual channel monitoring.
- Physical Size: 69 x 94 x 80 mm (2.72 x 3.7 x 3.2 inches).
Frequently Asked Questions (FAQ)
-
Q: Is the Honeywell TC-FID161 brand new and original?
A: Yes, we supply only 100% new, original Honeywell modules with full factory traceability. -
Q: What is the typical lead time for this module?
A: We dispatch within 5 days from our warehouse. Express shipping takes 2–4 additional days. -
Q: Can I use this module with 12 Vdc sensors?
A: No, the ON-state requires minimum 10 Vdc, but nominal operation is 24 Vdc. Verify sensor output levels. -
Q: How do I change the input filter time?
A: You set the filter via the output image table in your control logic – see manual for register mapping. -
Q: Are the channels isolated from each other?
A: No, all 16 channels share a common ground; they are non-isolated within the group. -
Q: What wire gauge should I use?
A: Use 12 AWG (4 mm²) stranded wire with 90 °C insulation for all field terminations. -
Q: Does the module support Class I Division 2 areas?
A: Yes, it carries Class I Division 2 and Zone 2 Group IIC agency certifications.
Contact Information Inquiries: sales@nex-auto.com , +86 153 9242 9628
Partner NexAuto Technology Limited : https://www.nex-auto.com/
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.