Home
SDV531-L63 Digital Output Module YOKOGAWA 8-Ch Isolated
1
/
of
3
SDV531-L63 Digital Output Module YOKOGAWA 8-Ch Isolated
No reviews
In stock (15 units), ready to be shipped
-
Vendor:
Yokogawa
-
Type:
Digital Output Module
-
Country of Origin:
ID
-
Dimensions:
11*13*3cm
- Weight:
300 g
- Tags: Digital output module
YOKOGAWA SDV531-L63 Digital Output Module
Technical Specifications Overview
- Model: YOKOGAWA SDV531-L63 (8-channel isolated DO module, long-distance type).
- Rated Voltage: 24 V DC +20% / -10% (range 21.6 to 28.8 V DC).
- External Supply Rating: 24 V DC, 5 A minimum.
- Output Format: Current source (sourcing).
- Max Load Current: 0.6 A per output line; 4.8 A total for all outputs.
- Min Load Current: 35 mA per output line.
- Load Resistance Range: 40 to 685 Ω.
- Output Response Time: 30 ms (max).
- Leakage Current (OFF): 1.6 mA maximum.
- Withstand Voltage: 2 kV AC (output to system) for 1 minute.
- Temperature Range: -20 °C to +70 °C (compliant with ISA G3).
- Current Consumption: 280 mA (5 V DC) / 140 mA (24 V DC).
- Weight: Approx. 0.28 kg (terminal block) / 0.34 kg (with cable adapter).
Frequently Asked Questions (FAQ)
-
Q: Can I use the SDV531-L63 with a YOKOGAWA Centum VP system?
A: Yes, the SDV531-L63 is fully compatible with all YOKOGAWA DCS series that use the standard backplane. -
Q: What does the "long-distance type" (-L suffix) mean for this module?
A: The -L suffix optimizes the SDV531-L63 for longer cable runs, typically up to 500 meters, without signal degradation. -
Q: Does this module support sinking outputs as well?
A: No, this model provides current source (sourcing) outputs only. It is not configurable for sinking. -
Q: How do the built-in diagnostic functions work?
A: The module continuously monitors field wiring conditions and reports open-circuit or short-circuit faults without external components. -
Q: Do you have stock for this model right now?
A: Yes, we keep the SDV531-L63 in stock for immediate shipment. -
Q: What is the return policy if the module does not fit my application?
A: We offer a 30-day return policy – just contact us for an RMA number. -
Q: Can I use a 24 V DC power supply with higher current capacity?
A: Yes, you can use a supply with higher capacity as long as the voltage stays within 21.6–28.8 V DC. -
Q: What is the maximum load resistance for reliable operation?
A: The load resistance range is 40 to 685 Ω – ensure your load falls within this range for proper current sourcing.
Contact Information Inquiries: sales@nex-auto.com , +86 153 9242 9628
Partner NexAuto Technology Limited: https://www.nex-auto.com/
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.