Home
Allen-Bradley 1762-OA8 Solid-State Output Module | 8-Point AC
1
/
of
3
Allen-Bradley 1762-OA8 Solid-State Output Module | 8-Point AC
No reviews
In stock (20 units), ready to be shipped
-
Vendor:
Allen-Bradley
-
Type:
Output Module
-
Country of Origin:
USA
-
Dimensions:
9*4*8cm
- Weight:
310 g
- Tags: Output module
Allen-Bradley 1762-OA8 Solid-State Output Module Overview
Key Technical Specifications
- Brand: Allen-Bradley, a trusted leader in industrial automation and control components.
- Catalog Number: The 1762-OA8 provides 8 AC triac outputs for reliable solid-state switching.
- Operating Voltage: Supports 85 to 265 Volts AC at 47 to 63 Hertz for worldwide compatibility.
- Input Power: Requires 100 to 240 Volts AC for module operation.
- Output Configuration: Features 8 AC triac outputs organized into 2 commons for flexible wiring.
- Bus Current: Draws maximum 115 mA at 5 Volts DC from the backplane.
- Heat Dissipation: Generates only 2.9 Watts for energy-efficient operation.
Electrical Characteristics
- Voltage Drop: Maximum 1.5 Volts at 0.5 Amps for efficient power delivery to loads.
- Minimum On-State Current: Requires 10 mA minimum load current for proper triac operation.
- Operating Frequency: Supports standard line frequencies of 47 to 63 Hertz.
- Operating Temperature: Functions reliably from 32 to 131 degrees Fahrenheit (0 to 55 degrees Celsius).
- Non-Operating Temperature: Withstands storage from -40 to 185 degrees Fahrenheit (-40 to 85 degrees Celsius).
Frequently Asked Questions (FAQ)
-
Can I return this module if it doesn't fit my application?
Yes, we support returns within 30 days, provided the item remains in its original condition. -
What is the difference between the 1762-OA8 and similar output modules?
The 1762-OA8 specifically provides 8 AC triac outputs with 85-265V AC operating range, ideal for AC load switching without mechanical contacts. -
Which controllers are compatible with this output module?
The 1762-OA8 works with MicroLogix 1100, MicroLogix 1200, and MicroLogix 1400 systems as an expansion module. -
What is the minimum load current for proper operation?
This module requires a minimum on-state current of 10 mA to ensure reliable triac switching. -
Can I remove the finger-safe cover after wiring?
No, once you remove the cover and wire the terminals, the cover cannot be reinstalled due to wire positioning.
For inquiries or to place an order, please contact us:
Email: sales@nex-auto.com
WhatsApp: +86 153 9242 9628
Partner: NexAuto Technology Limited
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.