Skip to product information
1 of 3

XNX-UTAE-NNNNN Honeywell Gas Transmitter Electrochemical Interface

In stock (14 units), ready to be shipped
  • Vendor:

    Honeywell

  • Type:

    XNX Universal Transmitter

  • Country of Origin:

    USA

  • Dimensions:

    16*19*11cm

  • Weight:

    5000 g

  • Tags: Xnx universal transmitter

XNX-UTAE-NNNNN Universal Gas Transmitter by Honeywell

  • Brand & Model: Honeywell XNX-UTAE-NNNNN (XNX Universal Gas Transmitter).
  • Approval & Entry: UL/CSA certified with ¾" NPT cable entry.
  • Material & Personality: Aluminium housing; Electrochemical Cartridge interface with IS barrier.
  • Sensor Input: Designed for XNX toxic and oxygen electrochemical sensors.
  • Output: 4-20mA with HART® (no Modbus, no local HART installed).
  • Weight: 2.8 Kg (compact and lightweight).

Key Technical Specifications

  • Sensor Interface: Electrochemical Cartridge with integrated IS barrier and adaptor.
  • Compatible Sensors: XNX toxic gas sensors and oxygen sensors.
  • Output Signal: 4-20 mA with HART® protocol.
  • Housing Material: Aluminium – lightweight with good thermal conductivity.
  • Cable Entry: ¾" NPT thread.
  • Operating Temperature: -40°C to +65°C (-40°F to +149°F).
  • Operating Humidity: 0-99% RH (non-condensing).
  • Operating Pressure: 90-110 kPa.
  • Storage Conditions: -40°C to 75°C (-40°F to 167°F), 0-99% non-condensing.
  • Dimensions: 16 cm x 19.7 cm x 11.4 cm (6.1" x 7.8" x 4.5").

Frequently Asked Questions (FAQ)

  • Q: What sensors work with the XNX-UTAE-NNNNN?
    A: It supports XNX toxic gas sensors and oxygen sensors that use the electrochemical cartridge format.
  • Q: What is the purpose of the IS barrier?
    A: The intrinsically safe barrier limits energy to the sensor for safe operation in hazardous areas.
  • Q: Does this model include a sensor?
    A: No, the sensor (NNN) is not included. You must order the compatible XNX electrochemical sensor separately.
  • Q: What approvals does the XNX-UTAE-NNNNN carry?
    A: It carries UL and CSA certifications for North American markets.
  • Q: Can I use this transmitter with a 4-20mA sensor from another brand?
    A: This version is specifically designed for XNX electrochemical cartridges, not for generic 4-20mA inputs.
  • Q: What power supply does it require?
    A: It operates on 12-32 V DC (nominal 24 V DC).
  • Q: Is the XNX-UTAE-NNNNN suitable for SIL applications?
    A: Please refer to the Honeywell safety manual for SIL certification details.

Contact Information Inquiries: sales@nex-auto.com , +86 153 9242 9628
Partner NexAuto Technology Limited : https://www.nex-auto.com/

Download PDF Document

Click to download PDF

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most