Skip to product information
1 of 3

TC-FOR081 Honeywell 8-Channel Relay Output Module 240V

In stock (15 units), ready to be shipped
  • Vendor:

    Honeywell

  • Type:

    Analog Output Module

  • Country of Origin:

    USA

  • Dimensions:

    10*13*5cm

  • Weight:

    500 g

  • Tags: Analog output module

TC-FOR081 | Honeywell | 8-Channel Relay Output Module

Key Output & Contact Specifications

  • Outputs: 8 Form A normally-open relays with full channel-to-channel isolation.
  • Off-state leakage: 1 mA maximum through the internal snubber circuit.
  • Resistive load ratings: 2 A at 5–30 Vdc; 0.5 A at 48 Vdc; 0.25 A at 125 Vdc; 2 A at 125 Vac; 2 A at 240 Vac.
  • Inductive load ratings: 2 A steady-state at 5–30 Vdc (L/R=7ms); 0.5 A at 48 Vdc; 0.25 A at 125 Vdc; 2 A at 125 Vac (PF=0.4); 2 A at 240 Vac (PF=0.4) with 15 A make capability.
  • Maximum power ratings: 480 W for 240 Vac resistive; 250 W for 125 Vac; 60 W for 30 Vdc; 24 W for 48 Vdc; 31 W for 125 Vdc.
  • Isolation voltage: 2550 Vdc for 1 second between any two contacts; 2550 Vdc customer load to logic; 2550 Vdc load to 24 Vdc supply; 850 Vdc between 24 Vdc supply and logic.
  • Switching delays: OFF-to-ON 8 ms max; ON-to-OFF 26 ms max.
  • Contact life: minimum 100,000 operations at rated loads.
  • Inrush current: 15 A maximum for short-duration surges.

Timing, Fusing & General Specifications

  • Operate/Release time: 10 ms maximum; bounce time 1.2 ms mean.
  • Minimum contact load: 100 µA at 100 mV dc for reliable low-level switching.
  • Switching frequency: 1 operation per 3 seconds (0.3 Hz) at rated load.
  • Fusing recommendation: use a fused terminal base with 3.0 A Littelfuse 239003; module outputs are not internally fused.
  • External DC supply: 24 Vdc nominal, 19.2–31.2 Vdc range (5% AC ripple), 125 mA max.
  • Power dissipation: 5.5 W maximum; thermal dissipation 18.8 BTU/hr.
  • Indicators: 8 yellow LEDs for per-channel status (logic-driven).
  • Keyswitch position: 9 for module addressing.

Environmental & Mechanical Durability

  • Operating temperature: 0 to 55 °C (32 to 131 °F).
  • Storage temperature: -40 to 85 °C (-40 to 185 °F).
  • Humidity: 5 to 95% non-condensing for versatile plant environments.
  • Shock tolerance: 12 g peak operating, 50 g non-operating (11 ms pulse).
  • Vibration: tested to 2 g @ 10–500 Hz per IEC 68-2-6.
  • Wire size: accepts 12 AWG (4 mm²) stranded with 1.2 mm insulation max.
  • Dimensions: 46 mm x 94 mm x 53 mm (1.8 in x 3.7 in x 2.1 in).

Installation & Field Wiring

  • Mount the TC-FOR081 on a standard DIN rail inside your cabinet.
  • Use a fused terminal base with a 3.0 A Littelfuse 239003 for external protection.
  • Connect loads per the voltage/current ratings; ensure proper wire gauge (12 AWG max).
  • Observe isolation boundaries: keep customer load wiring separate from logic circuits.
  • Allow adequate cooling; derate if ambient temperature exceeds 55 °C.
  • Set the keyswitch to position 9 for proper module addressing in the backplane.

Package Contents

  • TC-FOR081 8-channel relay output module.
  • DIN-rail mounting clips and hardware.
  • Product documentation with wiring diagrams and contact ratings.
  • Quick start guide for installation and diagnostic checks.

Shipping & Delivery Options

  • We stock the TC-FOR081 in our warehouse for immediate dispatch.
  • Choose from FedEx, UPS, or DHL for express shipping worldwide.
  • We process all orders within 5 business days after order confirmation.
  • All shipments include full tracking and insurance coverage.

Frequently Asked Questions

  • Is the TC-FOR081 brand new and original? Yes, we supply only 100% new, original Honeywell modules.
  • What is the typical lead time? We ship within 5 days; expedited options via DHL, UPS, or FedEx.
  • Does this module provide channel-to-channel isolation? Yes, all 8 relays are fully isolated from each other.
  • What is the maximum switching frequency? 0.3 Hz (one operation per 3 seconds) at rated load.
  • Do I need external fusing? Yes, we recommend a fused terminal base with a 3.0 A Littelfuse 239003.
  • What is the minimum contact load for reliable switching? 100 µA at 100 mV dc.
  • Do you accept returns? Yes, we support a 30-day return policy for unused items in original packaging.

Contact Information: For inquiries, please email sales@nex-auto.com or call +86 153 9242 9628 (WhatsApp).

Partner: NexAuto Technology Limited

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most