Skip to product information
1 of 3

XNXXSZ1SS Honeywell Ozone Transmitter 0-0.4 ppm Modbus

In stock (14 units), ready to be shipped
  • Vendor:

    Honeywell

  • Type:

    Smart Sensor Cartridges

  • Country of Origin:

    USA

  • Dimensions:

    16*20*10cm

  • Weight:

    4000 g

  • Tags: Smart sensor cartridges

XNXXSZ1SS Honeywell XNX Ozone Transmitter – 0.4 ppm Modbus RTU

Key Technical Specifications

  • Brand & Model: Honeywell Analytics XNXXSZ1SS – ozone transmitter.
  • Gas & Range: O₃ (Ozone) with fixed 0.400 ppm full scale.
  • Accuracy & LOD: ±0.003 ppm accuracy; lower detectable limit = 0.032 ppm.
  • Response Times: T50 < 15 sec, T90 < 60 sec for rapid alarm activation.
  • Modbus Output: Isolated RS485 with baud rates from 1200 to 19.2K.
  • Protocol & Nodes: Modbus RTU, supports up to 254 XNX transmitters.
  • Temperature Range: Operates from -20°C (-4°F) up to 55°C (131°F).
  • Calibration: Default cal gas = 0.200 ppm (30-70% of span).

Installation & Connectivity

  • The Modbus output module installs inside the display housing at the factory.
  • A qualified service engineer can also perform field installation as needed.
  • Connections use RS485+, RS485-, and Drain terminals for reliable data transfer.
  • This isolated physical layer ensures robust communication in industrial settings.
  • The XNXXSZ1SS does not support relays or Foundation Fieldbus options simultaneously.

Package Contents & Shipping

  • Each package includes one XNXXSZ1SS ozone transmitter with Modbus module.
  • We also include a quick-start guide and terminal block connectors.
  • We ship all orders via FedEx, UPS, or DHL for fast global delivery.
  • We hold stock and dispatch within 5 working days after order confirmation.

Frequently Asked Questions (FAQ)

  • Is the XNXXSZ1SS brand new?
    Yes, we supply only brand new, factory-sealed units.
  • Do you keep this ozone transmitter in stock?
    Yes, we maintain stock for immediate shipping.
  • How do you ship the XNX transmitter?
    We use FedEx, UPS, or DHL with tracking numbers.
  • What is the return policy for this item?
    We accept returns within 30 days of delivery.
  • Can I use this sensor with a 3-wire RS485 network?
    Yes, it uses RS485+, RS485-, and Drain connections.
  • What is the default calibration gas value?
    The factory default cal point is 0.200 ppm ozone.
  • What is the lower detectable limit?
    The LOD is 0.032 ppm for reliable low-level detection.

Contact Information Inquiries: sales@nex-auto.com , +86 153 9242 9628

Partner NexAuto Technology Limited: https://www.nex-auto.com/

Download PDF Document

Click to download PDF

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most