Key Technical Specifications

  • Brand: ABB
  • Model: V18345-1004210001
  • Product Type: Electro-Pneumatic Positioner
  • Input Signal: Two-wire technology, nominal range 4...20 mA
  • Split Range: Configurable between 20% and 100% of nominal range
  • Maximum Input: 25 mA / 30 V
  • Minimum Input: 3.4 mA without analog position feedback, 3.5 mA with analog position feedback
  • Start Point: 3.8 mA
  • Load Voltage at 20 mA: 8.7 V DC without explosion protection, 9.7 V DC for intrinsically safe device
  • Impedance at 20 mA: 435 ohms without explosion protection, 485 ohms for intrinsically safe device
  • Digital Input: Control voltage 24 V DC (12...30 V DC), logical "0" at 0...10 V DC, logical "1" at 12...30 V DC, max current 4 mA
  • Digital Output: Control circuit to DIN 19234/NAMUR, supply voltage 5...11 V DC, current < 1.0 mA for logical "0", current > 2.0 mA for logical "1"
  • Output Range: 0...6 bar (0...90 psi)
  • Air Capacity at 1.4 bar: 5.0 kg/h = 3.9 Nm3/h = 2.3 scfm
  • Air Capacity at 6 bar: 13 kg/h = 10 Nm3/h = 6.0 scfm
  • Output Function: Single or double acting actuators, fail freeze on electrical power failure
  • Shut-off Values: End position 0% = 0...45%, end position 100% = 55...100%
  • Angle of Rotation: 25...120° for rotary actuators, optional 270°; 25...60° for linear actuators
  • Travel Limit: Freely configurable within 0...100% of total travel, minimum range > 20%
  • Travel Time Prolongation: 0...200 seconds, separately for each direction
  • Positioning Time Limit: 0...200 seconds monitoring parameter
  • Supply Pressure: 1.4...6 bar (20...90 psi)
  • Air Consumption: < 0.03 kg/h / 0.015 scfm, independent of supply pressure
  • Characteristic Curve: Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1, freely configurable with 20 reference points
  • Characteristic Deviation: ≤ 0.5%
  • Tolerance Band: 0.3...10%, adjustable
  • Dead Band: 0.1...10%, adjustable
  • Resolution: > 4000 steps (A/D conversion)
  • Sample Rate: 20 msec
  • Ambient Temperature Influence: ≤ 0.5% for every 10 °C change
  • Vibration Influence: ≤ ± 1% up to 10 g and 80 Hz
  • Seismic Requirements: Meets DIN/IEC 68-3-3 Class III for strong and strongest earthquakes
  • Mounting Orientation Influence: No effect
  • Operating Temperature Range: -40...+85 °C
  • Communication: HART Protocol 5.1, local connector for LKS adapter, HART communication via 20 mA signal line with FSK modem
  • Housing: Aluminium, varnished, IP 65 (NEMA 4X)
  • Mounting: Linear actuators per DIN/IEC 534 / NAMUR, rotary actuators per VDI/VDE 3845, integral mounting ready
  • Connections: Cable thread 1/2-14 NPT, air pipe thread 1/4-18 NPT
  • Option Module: Without analog or digital position feedback
  • Mechanical Kit: Without digital position feedback
  • Design: Standard varnish and coding
  • Weight: 1.7 Kg
  • Explosion Protection: ATEX EEx n A II T6, Zone 2, TÜV 02 ATEX 1943 X
  • Approvals: ATEX, FM, CSA, IECEx, suitable for SIL2 safety loops
  • Directives: EMC Directive 89/336/EEC, CE conformity marking

FAQ

  • Q: What is the input signal range of the V18345-1004210001?
    A: It uses a two-wire 4...20 mA nominal range with split range configuration from 20% to 100%.
  • Q: Does this positioner support HART communication?
    A: Yes, it includes an FSK module for HART communication and supports HART Protocol 5.1.
  • Q: What explosion protection does this model carry?
    A: It carries ATEX EEx n A II T6 certification for Zone 2 hazardous areas.
  • Q: What is the safe position on electrical power failure?
    A: This model provides fail freeze, which blocks the actuator in its last position.
  • Q: What is the operating temperature range?
    A: The positioner works from -40...+85 °C for operation, storage, and transport.
  • Q: What air supply pressure does it require?
    A: It needs 1.4...6 bar (20...90 psi) and must not exceed the actuator maximum pressure.
  • Q: What is the resolution of the A/D conversion?
    A: The resolution exceeds 4000 steps with a 20 msec sample rate.
  • Q: Is this unit suitable for SIL2 safety loops?
    A: Yes, it meets SIL2 requirements and holds ATEX, FM, CSA, and IECEx approvals.
  • Q: What is the air consumption?
    A: Air consumption stays below 0.03 kg/h or 0.015 scfm, independent of supply pressure.
  • Q: What is the weight of the positioner?
    A: The unit weighs 1.7 Kg.

Contact Information

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most