Home
IS230SDIIH1A GE Mark VIe Contact Input Module 16-Channel
1
/
of
3
IS230SDIIH1A GE Mark VIe Contact Input Module 16-Channel
No reviews
In stock (16 units), ready to be shipped
-
Vendor:
General Electric
-
Type:
Contact Input Module
-
Country of Origin:
USA
-
Dimensions:
18*18*6cm
- Weight:
500 g
- Tags: Contact input module
IS230SDIIH1A Simplex Contact Input Module from GE Energy
Technical Specifications
- Brand: GE Energy
- Model: IS230SDIIH1A
- Product Type: Simplex Contact Input with Point Isolation Terminal Board
- Series: Mark VIe
- Number of Channels: 16 contact voltage input channels
- Voltage Range: 14 to 32 V dc
- Channel Voltage Levels: 48 V dc, 125 V dc, 115 V ac rms, and 230 V ac rms
- Maximum Lead Resistance: 15 Ohms
- Outputs: 24 V dc
- Mounting: DIN-rail mounting
- Technology: Surface mount
- Circuit Protection: Spray-based conformal coat
- Operating Temperature: -30 to 65°C
- Size: 15.9 cm high x 17.8 cm
- Weight: 2 lbs
- Country of Origin: United States
- Manual: GEH-6721L
- Availability: In stock
Functional Description
- The module provides 16 point-isolated voltage detection circuits for contact sensing.
- It senses voltages across relay contacts, fuses, switches, and other contact types.
- It uses an IS200SDII terminal board plus a PDII I/O pack.
- Each channel accepts 48 V dc, 125 V dc, 115 V ac rms, or 230 V ac rms.
- Three terminals exist for each contact input channel.
- Pluggable Euro-style box-type terminal blocks simplify field wiring.
- A connector accepts different WDII option boards for system wetting.
- All 16 channels stay point-isolated when you use PDII with SDII only.
Operation Details
- The sensing circuit converts voltage at the TB input into an isolated digital signal.
- Firmware calculates the voltage present at the TB input.
- It declares the contact status as on or off based on voltage presence.
- Each input stays isolated from the others for reliable signal separation.
- All inputs are point-isolated and system-isolated without an option board.
- With WDIIH1, channels support system wetting at 24 V dc or AC rms levels.
- AC frequency range for 50 Hz and 60 Hz is ±3 Hz.
- Removing the channel fuse allows use as a point-isolated signal path.
WDII Option Board Compatibility
- WDIIH1: Supports system wetting with 24 V dc, 115 V ac rms, or 230 V ac rms across all 16 channels.
- WDIIH2: Supports system wetting with 48 V dc across all 16 channels.
- WDIIH3: Supports system wetting with 125 V dc only; all channels are group-isolated.
- Each channel can be individually configured as point-isolated on WDIIH1 and WDIIH2.
- A mix of point isolation and group isolation is possible on WDIIH1 and WDIIH2.
- WDII boards include an isolated voltage detector circuit to monitor wetting voltage.
- WDIIH boards offer field line fault monitoring with one or two field resistors.
- PDII can detect open field wiring or an open fuse on WDII with a parallel resistor.
Group Isolated Input Signals
- Contact input channels receive wetting voltage through a WDII option board.
- WDIIH1A provides 115 V/240 V ac rms, 50/60 Hz, and 24 V dc wetting voltage.
- Individual fuses exist in each supply line for protection.
- Wetting voltage connects through JE1 or JE2 parallel connectors.
- Connect pin 1 of JE1 to the positive and pin 3 to the negative.
- Do not reverse polarity at JE1 or JE2.
- Group isolation replaces point isolation when a WDII board connects.
- The system wetting voltage then comes through the WDII board.
Installation Guide
- Mount the IS230SDIIH1A on a standard DIN rail.
- Connect field wiring to the pluggable Euro-style box-type terminal blocks.
- Use three terminals per contact input channel for proper wiring.
- Attach the PDII I/O pack to the IS200SDII terminal board.
- Add a WDII option board when system wetting is required.
- Verify the channel fuse is present before enabling system wetting.
- Check the JE1 or JE2 polarity before applying wetting voltage.
- Confirm the operating temperature stays within -30 to 65°C.
Packing List
- One IS230SDIIH1A Simplex Contact Input Module
- One IS200SDII terminal board
- One PDII I/O pack
- Anti-static protective packaging
- Protective foam or cushioning material
- Outer shipping carton
- Product label with model and series information
Shipping and Support
- We keep this item in stock and ship it within 5 days.
- We use common express methods such as FedEx, UPS, and DHL.
- We support returns within 30 days.
- This item is brand new and original.
- Contact us for technical questions or order support.
FAQ
-
Q: What is the IS230SDIIH1A used for?
A: It senses voltages across relay contacts, switches, fuses, and other contacts in Mark VIe systems. -
Q: How many channels does it provide?
A: It provides 16 contact voltage input channels with point isolation. -
Q: What voltage range does the module support?
A: It supports 14 to 32 V dc with channel levels of 48 V dc, 125 V dc, 115 V ac rms, and 230 V ac rms. -
Q: What is the maximum lead resistance?
A: The maximum lead resistance is 15 Ohms. -
Q: What is the operating temperature range?
A: The operating temperature range is -30 to 65°C. -
Q: How does the module mount?
A: It mounts on a DIN rail using surface mount technology. -
Q: Which option boards work with this module?
A: The WDIIH1, WDIIH2, and WDIIH3 option boards work with the SDII system. -
Q: Can I mix point isolation and group isolation?
A: Yes, WDIIH1 and WDIIH2 allow a mix of point isolation and group isolation. -
Q: What is the product condition?
A: The product is brand new and original. -
Q: How fast do you ship?
A: We ship within 5 days after order confirmation. -
Q: Which shipping methods do you use?
A: We use common express methods such as FedEx, UPS, and DHL. -
Q: What is the return policy?
A: We support returns within 30 days.
Contact Information
- Inquiries: sales@nex-auto.com
- Phone / WhatsApp: +86 153 9242 9628
- Partner: NexAuto Technology Limited
Fast & Reliable Shipping
Quick worldwide delivery
keeps your automation projects on schedule.
Genuine & Trusted
All components are 100% authentic
ensuring reliable performance for your systems.
- Express Delivery
- 12 Months Warranty
- 30 Days Easy Returns

Customer Support
Get Help When You Need It Most
Here to Assist Your Automation Needs
Contact us for pricing, product details, or order assistance — our experts are available to help.
Know Your Return Rights
You have 30 days to return a product if it doesn’t meet your requirements. See the full policy for details.