Product Overview: Honeywell 900H32-0102 Digital Output Module

Electrical Specifications

  • Output Channels: 32 channels of current sourcing, high-side drivers.
  • Operating Voltage: Wide range from 10.5 to 32 VDC.
  • Peak Voltage: Maximum withstand voltage of 32 VDC.
  • ON Voltage Drop: Low drop of 0.15 VDC at a 0.5 A load.
  • Current per Point: 0.5 A maximum per individual output channel.
  • Module Current: 12 A maximum total per module for resistive loads.

Channel Configuration & Protection

  • Output Groups: Channels are arranged in 2 groups of 16 outputs.
  • Galvanic Isolation: Provides isolation between the two channel groups.
  • Overload Protection: Integrated active current limiting protection.
  • Protection Groups: Current limiting in 4 groups of 8 channels each.
  • Fault Recovery: No power cycle needed to reset after a fault condition.
  • Special Note: Outputs 17-32 cannot be used for TPO, PPO, or TPSC functions.

Load Specifications

  • Resistive Load: 0.5 A per point, 6 A max per group, 12 A module total.
  • Incandescent Lamp: 0.25 A per point with 5 mH maximum inductance.
  • Output Type: High-side driver (current sourcing) configuration.
  • Application: Suitable for valves, motors, alarms, and status indicators.

Physical Specifications

  • Dimensions: Compact size: 137mm H x 35.6mm W (5.4" x 1.4").
  • Weight: Lightweight design at only 0.18 kg.
  • Mounting: Designed for standard DIN rail or panel mounting.
  • Connections: Uses industrial-grade terminal connectors for reliability.

Frequently Asked Questions (FAQ)

  • Q: How many output channels does the 900H32-0102 have?
    A: It provides 32 digital output channels for 24VDC devices.
  • Q: What is the maximum current per output point?
    A: Each point can handle 0.5 Amps maximum continuous current.
  • Q: What type of output driver does it use?
    A: It uses a high-side, current sourcing driver configuration.
  • Q: Does it have overload protection?
    A: Yes, it features integrated active current limiting protection.
  • Q: Are all 32 channels identical in function?
    A: Outputs 17-32 have restrictions for TPO/PPO/TPSC applications.
  • Q: What is the total current capacity of the module?
    A: The total maximum current is 12 Amps for resistive loads.

Contact Information for Inquiries:
For sales, technical support, or stock availability, please email us at sales@nex-auto.com or message us on WhatsApp at +86 153 9242 9628.

Partner: NexAuto Technology Limited

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most