Перейти к информации о продукте
1 из 3

1756-A13 ControlLogix Chassis Allen-Bradley

В наличии (20 единиц), готово к отправке
  • Продавец:

    Allen-Bradley

  • Тип:

    ControlLogix Chassis

  • Country of Origin:

    USA

  • Dimensions:

    58.8*16.9*14.5cm

  • Weight:

    1900 g

  • Теги: Controllogix chassis

Allen-Bradley 1756-A13 ControlLogix Chassis

Chassis Configuration & Layout

  • Total Slot Capacity: 13 module slots for maximum flexibility
  • Power Supply Location: Dedicated left-side slot (does not count toward 13 slots)
  • Module Placement: Any ControlLogix module in any slot position
  • Mounting Tabs: Eight secure mounting points for stable installation
  • Slot Fillers: 1756-N2 modules required for all unused slots

Power Distribution System

  • 5.1V DC Backplane: 15A chassis total / 6A per slot maximum
  • 24V DC Backplane: 2.8A chassis total / 2.8A per slot maximum
  • 3.3V DC Backplane: 4A chassis total / 4A per slot maximum
  • 1.2V DC Backplane: 1.5A chassis total / 1.5A per slot maximum
  • Power Dissipation: 5.4 Watts maximum under full load

Environmental Specifications

  • Operating Temperature: 0°C to +60°C (+32°F to +140°F)
  • Storage Temperature: -40°C to +85°C (-40°F to +185°F)
  • Humidity Range: 5% to 95% relative humidity (non-condensing)
  • Vibration Resistance: 2g @ 10-500 Hz during operation
  • Shock Rating: 30g operational shock withstand capability

Electrical Installation Details

  • Functional Earth Ground: 8.3 mm² (8 AWG) copper wire minimum
  • Protective Earth Ground: 2.1 mm² (14 AWG) copper wire minimum
  • Wire Temperature Rating: 90°C (194°F) or greater required
  • Enclosure Type: Open-style for cabinet installation
  • Wiring Access: Front-accessible terminal blocks

Frequently Asked Questions

What makes the 1756-A13 suitable for large systems?

  • The 1756-A13 provides 13 expansion slots for comprehensive system configuration with multiple processors and specialized modules.

How does the backplane power distribution work?

  • The chassis delivers 15A total at 5.1V DC, with each slot capable of drawing up to 6A for power-intensive modules.

What are the cabinet space requirements?

  • You need minimum 30" W x 24" H x 8" D cabinet space for proper installation and maintenance access.

Can I mix different processor families?

  • Yes, the chassis supports Logix 5560, 5570, and 5580 processors in any combination across slots.

What safety features are included?

  • RIUP capability allows safe module replacement while powered, and electronic keying prevents installation errors.

How do I handle grounding requirements?

  • Use 8 AWG for functional earth ground and 14 AWG for protective earth ground, both rated for 90°C or higher.

What maintenance is required?

  • Regular inspection of connections, ensuring proper ventilation, and verifying ground integrity ensure long-term reliability.

For complete technical documentation and pricing, contact our automation specialists at: sales@nex-auto.com

Быстрая и надежная доставка

Быстрая доставка по всему миру

поддерживает ваши проекты автоматизации в графике.

Подлинный и надежный

Все компоненты на 100% аутентичны

обеспечивая надежную работу ваших систем.

  • Экспресс-доставка
  • 12 месяцев гарантии
  • 30 дней легкого возврата
Просмотреть детали продукта

Служба поддержки клиентов

Получите помощь, когда она вам больше всего нужна