Главная
1756-A13 ControlLogix Chassis Allen-Bradley
1
/
из
3
1756-A13 ControlLogix Chassis Allen-Bradley
No reviews
В наличии (20 единиц), готово к отправке
-
Продавец:
Allen-Bradley
-
Тип:
ControlLogix Chassis
-
Country of Origin:
USA
-
Dimensions:
58.8*16.9*14.5cm
- Weight:
1900 g
- Теги: Controllogix chassis
Allen-Bradley 1756-A13 ControlLogix Chassis
Chassis Configuration & Layout
- Total Slot Capacity: 13 module slots for maximum flexibility
- Power Supply Location: Dedicated left-side slot (does not count toward 13 slots)
- Module Placement: Any ControlLogix module in any slot position
- Mounting Tabs: Eight secure mounting points for stable installation
- Slot Fillers: 1756-N2 modules required for all unused slots
Power Distribution System
- 5.1V DC Backplane: 15A chassis total / 6A per slot maximum
- 24V DC Backplane: 2.8A chassis total / 2.8A per slot maximum
- 3.3V DC Backplane: 4A chassis total / 4A per slot maximum
- 1.2V DC Backplane: 1.5A chassis total / 1.5A per slot maximum
- Power Dissipation: 5.4 Watts maximum under full load
Environmental Specifications
- Operating Temperature: 0°C to +60°C (+32°F to +140°F)
- Storage Temperature: -40°C to +85°C (-40°F to +185°F)
- Humidity Range: 5% to 95% relative humidity (non-condensing)
- Vibration Resistance: 2g @ 10-500 Hz during operation
- Shock Rating: 30g operational shock withstand capability
Electrical Installation Details
- Functional Earth Ground: 8.3 mm² (8 AWG) copper wire minimum
- Protective Earth Ground: 2.1 mm² (14 AWG) copper wire minimum
- Wire Temperature Rating: 90°C (194°F) or greater required
- Enclosure Type: Open-style for cabinet installation
- Wiring Access: Front-accessible terminal blocks
Frequently Asked Questions
What makes the 1756-A13 suitable for large systems?
- The 1756-A13 provides 13 expansion slots for comprehensive system configuration with multiple processors and specialized modules.
How does the backplane power distribution work?
- The chassis delivers 15A total at 5.1V DC, with each slot capable of drawing up to 6A for power-intensive modules.
What are the cabinet space requirements?
- You need minimum 30" W x 24" H x 8" D cabinet space for proper installation and maintenance access.
Can I mix different processor families?
- Yes, the chassis supports Logix 5560, 5570, and 5580 processors in any combination across slots.
What safety features are included?
- RIUP capability allows safe module replacement while powered, and electronic keying prevents installation errors.
How do I handle grounding requirements?
- Use 8 AWG for functional earth ground and 14 AWG for protective earth ground, both rated for 90°C or higher.
What maintenance is required?
- Regular inspection of connections, ensuring proper ventilation, and verifying ground integrity ensure long-term reliability.
For complete technical documentation and pricing, contact our automation specialists at: sales@nex-auto.com
Быстрая и надежная доставка
Быстрая доставка по всему миру
поддерживает ваши проекты автоматизации в графике.
Подлинный и надежный
Все компоненты на 100% аутентичны
обеспечивая надежную работу ваших систем.
- Экспресс-доставка
- 12 месяцев гарантии
- 30 дней легкого возврата

Служба поддержки клиентов
Получите помощь, когда она вам больше всего нужна
Здесь, чтобы помочь с вашими потребностями в автоматизации
Свяжитесь с нами для получения информации о ценах, деталях продукта или помощи с заказом — наши эксперты готовы помочь.
Знайте свои права на возврат
У вас есть 30 дней, чтобы вернуть товар, если он не соответствует вашим требованиям. Ознакомьтесь с полной политикой для получения подробной информации.














