Honeywell 900H03-0202 8-Channel Triac AC Output Module

In stock (23 units), ready to be shipped

Honeywell 900H03-0202 AC Digital Output Module

The 900H03-0202 is an 8-channel solid-state AC output module for the Honeywell HC900 controller. It provides reliable switching for AC loads such as heaters, solenoids, and contactor coils with built-in protection.

Core Technical Specifications

  • Brand: Honeywell
  • Model Number: 900H03-0202
  • Product Type: Digital Output (DO) Module, AC Voltage
  • Outputs per Module: 8 Channels
  • Output Device: Triac (Zero-Voltage Switching)
  • Operating Voltage Range: 85 VAC to 240 VAC
  • Peak Voltage Rating: 250 VAC
  • AC Frequency Range: 47 Hz to 63 Hz
  • Galvanic Isolation: Per Output-to-Output, Output-to-Logic
  • Maximum Load Current: 2 A per Point, 8 A Maximum per Module (Resistive Load)
  • Minimum Load Current: 50 mA
  • Maximum Inrush Current: 15 A for 10 ms
  • Maximum Leakage Current: 4 mA (@240V AC, 60Hz), 1.2 mA (@100V AC, 60Hz), 0.9 mA (@100V AC, 50Hz)
  • ON Voltage Drop: < 2.0 VAC (>0.1 A), < 3.0 VAC (<0.1 A)
  • OFF to ON Response Time: 3 ms + 0.5 Line Cycle Max.
  • ON to OFF Response Time: 3 ms + 0.5 Line Cycle Max.
  • Transient Overvoltage Protection: MOV (Metal Oxide Varistor) per Output
  • Fuse Protection: 1 per Output, 3.15 A Time-Lag (Littelfuse 37413150410 or equivalent)
  • Fail-Safe Modes: Hold Last State, User-Defined Failsafe State
  • Shorting Comb: Available (P/N 900J02-0001 / 900J10-0001) for Common Voltage Source Wiring
  • Channel Status Indicator: Green LED per Channel (ON when output is active)
  • Module Status LED: Green Blinking (Active Scan), Red (Fault/Diagnostic)
  • Operating Temperature: 0°C to +60°C (Standard HC900 Range)

Module Features & Protection

  • Zero-crossing Triac switching minimizes electromagnetic interference (EMI) and extends load life.
  • Full isolation between each output and from controller logic enhances system safety and noise immunity.
  • Integrated MOV protects against voltage spikes and transients on the AC line.
  • Field-replaceable fuses (3.15A time-lag) protect each output from overload and short-circuit conditions.
  • Shorting comb accessory simplifies wiring when all outputs share a common AC voltage source.
  • Configurable failsafe operation ensures predictable behavior during communication loss or system fault.
  • Low leakage current minimizes energy waste and prevents unintended activation of sensitive loads.

Installation & Wiring Guidelines

  • Install in a compatible Honeywell HC900 rack. Ensure the AC line voltage is within 85-240V AC.
  • Use appropriate wire gauge for the load current (up to 2A per channel).
  • For inductive loads (solenoids, contactors), consider using an external snubber circuit to reduce EMI.
  • When using the shorting comb, connect the common AC source to the comb and then to the barrier terminal block.
  • Replace blown fuses only with the specified 3.15A time-lag type (e.g., Littelfuse 37413150410).
  • Observe the minimum load requirement of 50 mA; for smaller loads, a parallel load resistor may be necessary.
  • Ensure proper heat dissipation; do not exceed the total module current rating of 8A.

Typical Applications

  • Switching resistive heating elements.
  • Controlling solenoid valves and AC contactor coils.
  • Activating fans, pumps, and small AC motors.
  • General-purpose AC power control in industrial processes.

For fuse specifications or to order the Honeywell 900H03-0202, contact our technical sales team.

Contact: Email sales@nex-auto.com or WhatsApp +86 153 9242 9628.

Partner: NexAuto Technology Limited

© 2026 AutoNex Controls Limited. All rights reserved.

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most