Honeywell 900H02-0102 DC Digital Output Module

The 900H02-0102 is a 16-channel DC sinking output module for the Honeywell HC900 controller. It provides intelligent switching for DC loads with built-in electronic protection and diagnostic status indicators.

Core Technical Specifications

  • Brand: Honeywell
  • Model Number: 900H02-0102
  • Product Type: Digital Output (DO) Module, DC Voltage
  • Outputs per Module: 16 Channels
  • Output Type: Current Sinking, Low-Side Switch (Intelligent Power Switch - IPS)
  • Operating Voltage Range: 6.5 to 32 VDC (5.0 to 6.5 VDC @ <0.5A per channel)
  • Peak Voltage Rating: 34 VDC
  • Galvanic Isolation: 2 Groups of 8 Outputs
  • ON Voltage Drop: 0.3 VDC @ 1 A Load
  • Maximum Load Current: 1 A per Point, 8 A Maximum per Module (Resistive Load)
  • Maximum Incandescent Lamp Load: 0.5 A per Point (5 mH max inductance)
  • Maximum Leakage Current: 0.15 mA @ 32 VDC
  • Maximum Inrush Current: 4 A for 10 ms
  • Minimum Load: 0.0 mA (No Minimum Required)
  • OFF to ON Response Time: 6 ms (excluding controller scan & backplane transmission)
  • ON to OFF Response Time: 6 ms (excluding controller scan & backplane transmission)
  • Overload Protection: Electronic High Current & High Temperature Limiting; Reset requires cycling field power
  • Power Supply Loading (from Backplane): 5V; 340 mA, 24V; 0 mA
  • Status Indicators:
    • Green LED per Channel (Output ON)
    • Green Blinking Module LED (Active Scan)
    • Amber Blinking Module LED (Channels Forced)
    • Red Module LED (Fault/Diagnostic)
  • Operating Temperature: 0°C to +60°C (Standard HC900 Range)

Module Features & Protection

  • Low-side sinking outputs are ideal for interfacing with PLCs and devices that expect a common positive voltage.
  • Intelligent Power Switch (IPS) technology provides efficient switching with low voltage drop.
  • Electronic overload protection guards against short circuits and overtemperature conditions.
  • Clear multi-color module status LEDs indicate operational mode: normal scan, forced outputs, or faults.
  • Protection reset requires cycling the external field power, preventing automatic restart after a fault.
  • No external fuses required; protection is integrated electronically.
  • Grouped isolation (2 groups of 8) allows connection to two different DC power sources.

Installation & Wiring Guidelines

  • Install in a compatible Honeywell HC900 rack. Provide external DC power (6.5-32V) for the field loads.
  • Connect the external DC+ supply to the common positive of the field loads.
  • Connect the load between the output terminal (sinking side) and the DC- (common negative).
  • Wire outputs in groups of 8, each group to its own +V and COM terminals on the module.
  • Do not exceed 1A continuous current per output or 8A total per module.
  • For inductive loads, use external flyback diodes across the load to protect the output switch.
  • If an overload trips, disconnect the field power to reset the module's protection circuit.

Typical Applications

  • Driving indicator lamps, LED arrays, and small DC relays.
  • Controlling solenoid valves and low-power DC actuators.
  • Interfacing with other control systems requiring a sinking input signal.
  • General-purpose DC output control in machinery and automated systems.

For detailed wiring diagrams or to order the Honeywell 900H02-0102, contact our technical sales team.

Contact: Email sales@nex-auto.com or WhatsApp +86 153 9242 9628.

Partner: NexAuto Technology Limited

© 2026 AutoNex Controls Limited. All rights reserved.

Fast & Reliable Shipping

Quick worldwide delivery

keeps your automation projects on schedule.

Genuine & Trusted

All components are 100% authentic

ensuring reliable performance for your systems.

  • Express Delivery
  • 12 Months Warranty
  • 30 Days Easy Returns
View Product Details

Customer Support

Get Help When You Need It Most