Home
Allen-Bradley 1794-IA16 Flex I/O AC Input Module 16 Channel
1
/
di
3
Allen-Bradley 1794-IA16 Flex I/O AC Input Module 16 Channel
No reviews
Disponibile (18 unità), pronto per essere spedito
-
Venditore:
Allen-Bradley
-
Tipo:
Input Module
-
Country of Origin:
USA
-
Dimensions:
9.4*9.4*6.9cm
- Weight:
110 g
- Tag: Input module
Allen-Bradley 1794-IA16 Flex I/O 16-Channel AC Input Module
Core Technical Specifications
- Brand: Allen-Bradley
- Model: 1794-IA16 AC Digital Input Module
- Input Channels: 16 non-isolated AC input points
- Input Voltage Range: 74 to 132 Volts AC (120VAC nominal)
- On-State Current: 5.49 mA minimum, 14.81 mA maximum
- Off-State Voltage: 20 Volts AC maximum
- Nominal Input Current: 12 mA at 120 Volts AC
- FlexBus Current: 20 mA at 5V DC for backplane power
- Power Dissipation: 6.4 Watts maximum at 132V AC
Compatibility & Connectivity
- Communication Adapters: Works with 1794-AENT, 1794-AENTR (EtherNet/IP), 1794-ACN, 1794-ACNR (ControlNet), and 1794-ASB (Remote I/O)
- Terminal Bases: Requires compatible base: 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, or 1794-TBNK
- Keyswitch Position: Position 8 for proper module configuration
- Power Daisy-Chaining: Terminal bases allow power transfer between adjacent modules
Physical & Environmental Ratings
- Mounting: Standard DIN rail installation
- Operating Temperature: Reliable performance from 0 to 55°C (32 to 131°F)
- Storage Temperature: -40 to 85°C (-40 to 185°F)
- Vibration Resistance: 5g from 10 to 500 Hz per IEC standards
- Shock Resistance: 30g operating shock rating
- Dimensions: 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 inches)
- Isolation Voltage: 120V continuous, tested at 1,264V AC for 60 seconds
Frequently Asked Questions (FAQ)
-
Q: What voltage range does the 1794-IA16 support?
A: The 1794-IA16 accepts AC inputs from 74 to 132 Volts AC, with 120VAC as the nominal operating voltage. -
Q: Does this module work with Ethernet/IP systems?
A: Yes, it's fully compatible with EtherNet/IP adapters like the 1794-AENT and 1794-AENTR. -
Q: What terminal base do I need for installation?
A: You need one of these bases: 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, or 1794-TBNK. -
Q: Are the input channels isolated from each other?
A: No, the 1794-IA16 features 16 non-isolated input channels. -
Q: What is your shipping and return policy?
A: We ship within 5 business days and offer a 30-day return policy on all products.
For technical support, volume pricing, or compatibility questions, contact our automation specialists.
Contact Information Inquiries: Email sales@nex-auto.com or WhatsApp +86 153 9242 9628.
Partner: NexAuto Technology Limited
Spedizione Veloce e Affidabile
Consegna rapida in tutto il mondo
mantiene i tuoi progetti di automazione nei tempi previsti.
Autentico e Affidabile
Tutti i componenti sono 100% autentici
garantendo prestazioni affidabili per i tuoi sistemi.
- Consegna Espressa
- 12 Mesi di Garanzia
- Reso facile entro 30 giorni

Assistenza Clienti
Ricevi aiuto quando ne hai più bisogno
Qui per assisterti con le tue esigenze di automazione
Contattaci per prezzi, dettagli sul prodotto o assistenza per l'ordine — i nostri esperti sono disponibili per aiutarti.
Conosci i tuoi diritti di reso
Hai 30 giorni per restituire un prodotto se non soddisfa le tue esigenze. Consulta la politica completa per i dettagli.