Honeywell FC-TELD-0001 Earth Leakage Detector: Advanced Ground Fault Protection
- Precise earth fault detection for electrical safety
- Current monitoring technology identifies fault types
- Wide temperature operation from -40°C to +75°C
- Compact DIN rail design for easy installation
Product Overview
The Honeywell FC-TELD-0001 Earth Leakage Detector finds ground faults in power circuits. It monitors current changes to detect problems. This helps prevent electrical accidents and equipment damage.
Technical Specifications
Brand: Honeywell
Model: FC-TELD-0001
Product Type: Earth Leakage Detector Terminal
Detection Method: Current monitoring (0-20mA)
Operating Voltage: 24 VDC ±30%
Normal Current: 10 mA (no fault condition)
Max Current: 25 mA (limited by source)
Earth Voltage: +4.1 VDC typical
Detection Threshold: 0.6 mA incoming / 0.2 mA outgoing
Internal Resistor: 2.8 kΩ
Series Impedance: 250 Ω
Temperature Range: -40°C to +75°C
Dimensions: 80 x 20 x 70 mm
Wire Size: 0.2-4.0 mm² (solid), 0.2-2.5 mm² (stranded)
Installation Guide
Mounts on TS32/TS35 DIN rails
Requires only 21 mm rail space
8 mm wire strip length recommended
Standard screw terminal connections
Easy integration with control systems
Safety Certifications
CE marked for European compliance
TÜV approved for safety standards
Industrial grade construction
Quality tested for reliability
Compatibility Information
Works with RUSIO channel systems
Compatible with RUSLS channels
Requires 'earth fault detection' configuration
Integrates with Honeywell safety systems
Professional Questions Answered
How does the FC-TELD-0001 detect earth faults?
It monitors current changes from the normal 10mA reading, with variations indicating different fault types.
What temperature range can this detector handle?
It operates reliably in extreme temperatures from -40°C to +75°C.
How sensitive is the fault detection?
It detects currents as low as 0.2mA flowing from the unit or 0.6mA flowing into it.
What wiring is required for installation?
It accepts solid wires up to 4mm² or stranded wires up to 2.5mm² with 8mm strip length.
Can the detector be remotely controlled?
Yes, the control system can power it off to isolate from earth pins and remove fault current.
Shipping & Warranty
Fast delivery via FedEx, UPS, DHL
12-month product warranty
Quality assurance guaranteed
Technical support provided
Protect your electrical systems with the reliable FC-TELD-0001 earth leakage detector for enhanced safety monitoring.
Giao hàng nhanh chóng và đáng tin cậy
Giao hàng nhanh trên toàn thế giới
giúp các dự án tự động hóa của bạn đúng tiến độ.
Chính hãng & Đáng tin cậy
Tất cả các linh kiện đều là hàng chính hãng 100%
đảm bảo hiệu suất đáng tin cậy cho hệ thống của bạn.
- Giao hàng nhanh
- Bảo hành 12 tháng
- 30 Ngày Đổi Trả Dễ Dàng

Hỗ trợ khách hàng
Nhận trợ giúp khi bạn cần nhất
Sẵn sàng Hỗ trợ Nhu cầu Tự động hóa của Bạn
Liên hệ với chúng tôi để biết giá cả, chi tiết sản phẩm hoặc hỗ trợ đặt hàng — các chuyên gia của chúng tôi luôn sẵn sàng giúp đỡ.
Biết Quyền Lợi Trả Hàng Của Bạn
Bạn có 30 ngày để trả lại sản phẩm nếu nó không đáp ứng yêu cầu của bạn. Xem chính sách đầy đủ để biết chi tiết.