Schneider Electric 140DRC83000C Modicon Quantum Relay Output Module Overview

Key Technical Specifications

  • Manufacturer: Schneider Electric designs the 140DRC83000C for rigorous industrial automation environments.
  • Output Configuration: This relay discrete output module features 8 channels with 1 NO/NC contact composition in Form C arrangement.
  • Voltage Range: The module operates from 20 to 250 V AC, 30 to 150 V DC, and 5 to 30 V DC with 0.5 output word addressing.
  • Current Ratings: Maximum load current reaches 5 A at 250/30 V AC/DC resistive at 60°C, with 3 A standard AC/DC capability.
  • Specialized Loads: The 140DRC83000C handles 2 A at 250/30 V AC/DC for tungsten loads at 1/4 hp with cos phi = 0.4.
  • Low Current Operation: It supports 300 mA at 30-50 V DC resistive and 100 mA at 30-50 V DC with L/R = 10 ms inductive loads.
  • Surge Current: Each channel handles 20 A surge current for 10 ms capacitive loads during transient conditions.

Durability and Switching Performance

  • Mechanical Durability: The 140DRC83000C delivers 10,000,000 operational cycles for long-term reliability in demanding applications.
  • Electrical Durability: It achieves 200,000 cycles at 5 A 250 V AC resistive and 100,000 cycles at 5 A 30 V DC resistive.
  • Extended Durability Ratings: The module provides 100,000 cycles at 300 mA 30-150 V DC resistive and at 100 mA 30-150 V DC inductive.
  • Switching Frequency: It operates at 30 Hz for resistive loads with F = 0.5/I²L formula for inductive load switching.
  • Switching Capacity: The module supports 1250 VA resistive switching capacity for versatile industrial control applications.
  • Response Time: Maximum response time measures 10 ms from state 0 to 1 and 20 ms from state 1 to 0 on input open.

Protection and Environmental Specifications

  • Output Protection: Internal varistor provides overvoltage protection at 275 V for each output channel.
  • Isolation Rating: The module delivers 1780 Vrms AC for 1 minute and 2500 V DC isolation between channels.
  • Bus Isolation: It provides 1780 Vrms AC for 1 minute and 2500 V DC for 1 minute between channels and bus.
  • Operating Temperature: This output module functions reliably from 0 to 60 degrees Celsius in industrial settings.
  • Storage Temperature: It withstands storage conditions from -40 to 85 degrees Celsius without performance degradation.
  • Humidity Resistance: The 140DRC83000C supports up to 95% relative humidity without condensation during operation.
  • Altitude Capability: This unit operates safely at altitudes up to 5000 meters above sea level.
  • Protective Treatment: Conformal coating Humiseal 1A33 protects against moisture and environmental contaminants.

Certifications and Signaling Features

  • Product Certifications: The module holds RINA, FM Class 1 Division 2, GOST, C-tick, DNV, GL, RMRS, and ABS approvals.
  • Standards Compliance: It meets UL 508 and CSA C22.2 No 142 standards for industrial safety and performance.
  • EMC Compliance: It withstands 4 kV contact discharge and 8 kV air discharge per IEC 801-2 with 10 V/m field susceptibility to 2000 MHz.
  • Local Signaling: One green LED indicates Active bus communication, one red LED shows external fault detection.
  • Output Status: 8 green LEDs provide real-time input status monitoring for all 8 output channels.
  • Marking: The 140DRC83000C carries CE marking for international compliance.
  • Power Dissipation: Calculation follows 2.75 W + (0.5 x number of points on) formula for accurate thermal management.

Frequently Asked Questions (FAQ)

  • What is the contact configuration for the 140DRC83000C module? It features 1 NO/NC contact composition in Form C arrangement with 8 channels.
  • What voltage ranges does this relay output module support? It operates from 20 to 250 V AC, 30 to 150 V DC, and 5 to 30 V DC.
  • Does this module include conformal coating for environmental protection? Yes, the 140DRC83000C features Humiseal 1A33 conformal coating.
  • What is the mechanical durability rating for this module? It delivers 10,000,000 operational cycles for long-term reliability.
  • What certifications does the 140DRC83000C hold? It holds RINA, FM Class 1 Division 2, GOST, C-tick, DNV, GL, RMRS, and ABS approvals with CE marking.
  • Do you have this module in stock for immediate shipping? Yes, we maintain stock and ship within 5 days via FedEx, UPS, or DHL.
  • What is your return policy for the 140DRC83000C? We accept returns within 30 days of delivery for this product.
  • Is this product brand new and original from Schneider Electric? Yes, we supply only brand new original Schneider Electric modules.

© 2026 NexAuto Technology Limited. All rights reserved.
Original Source: https://www.nex-auto.com/
Contact: sales@nex-auto.com
Phone: +86 153 9242 9628

Giao hàng nhanh chóng và đáng tin cậy

Giao hàng nhanh trên toàn thế giới

giúp các dự án tự động hóa của bạn đúng tiến độ.

Chính hãng & Đáng tin cậy

Tất cả các linh kiện đều là hàng chính hãng 100%

đảm bảo hiệu suất đáng tin cậy cho hệ thống của bạn.

  • Giao hàng nhanh
  • Bảo hành 12 tháng
  • 30 Ngày Đổi Trả Dễ Dàng
Xem chi tiết sản phẩm

Hỗ trợ khách hàng

Nhận trợ giúp khi bạn cần nhất