1794-OB16 Flex I/O DC Output Module Overview
Technical Specifications of 1794-OB16
- Brand: Allen-Bradley
- Part Number: 1794-OB16
- Product Type: Flex I/O Digital DC Output Module
- Number of Outputs: 16 sourcing channels
- On-state Voltage Nominal: 24V DC
- On-state Voltage Range: 10 to 31.2V DC
- Output Current Rating: 8.0A total (500mA per channel max)
- Minimum On-state Current: 1mA per channel
- Maximum On-state Voltage Drop: 0.5V DC
- Maximum Off-state Leakage Current: 0.5mA
- Off-to-On Signal Delay: 0.5 milliseconds
- On-to-Off Signal Delay: 1.0 millisecond
- Surge Current: 2A for 50 ms (repeatable every 2 seconds)
- Continuous Isolation Voltage: 50V
- Flexbus Current: 80mA at 5V DC
- Power Dissipation: 5.3W at 31.2V DC maximum
- Thermal Dissipation: 18.1 BTU/hr. at 31.2V DC maximum
- Recommended External Fuse: SAN-O MQ4-800 mA
- Operating Temperature: 0 to 55°C (32 to 131°F)
- Storage Temperature: -40 to 85°C (-40 to 185°F)
- Vibration Rating: 5g at 10 to 500 Hz
- Operating Shock: 30g
- Dimensions: 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 inches)
- Weight: 78 grams (2.75 oz.)
Frequently Asked Questions (FAQ)
-
Do you have the 1794-OB16 in stock?
Yes, we keep the 1794-OB16 module in stock for immediate orders. -
What is your typical shipping time?
We ship within 5 days after confirming your order. -
Which carriers do you use for delivery?
We ship via FedEx, UPS, and DHL for fast and reliable service. -
Can I return this module if needed?
Yes, we support returns within 30 days from the delivery date. -
Why does this module have no internal fusing?
The 1794-OB16 requires external fusing. Use a SAN-O MQ4-800 mA fuse per channel for protection. -
Can I use this module with any Flex I/O adapter?
Yes, the 1794-OB16 works with all 1794 Flex I/O adapters for distributed I/O applications. -
What happens if I exceed 500mA per channel?
Exceeding 500mA per channel may damage the output. Install external fuses to prevent overcurrent.
For any inquiries, please contact us at sales@nex-auto.com or reach out via WhatsApp at +86 153 9242 9628. Partner with NexAuto Technology Limited: https://www.nex-auto.com/
Tez va Ishonchli Yetkazib berish
Tezkor butun dunyo bo‘ylab yetkazib berish
avtomatlashtirish loyihalaringizni jadvalga muvofiq saqlaydi.
Haqiqiy va Ishonchli
Barcha komponentlar 100% haqiqiy
sizning tizimlaringiz uchun ishonchli ishlashni ta'minlaydi.
- Tezkor yetkazib berish
- 12 oy kafolat
- 30 kunlik oson qaytarish imkoniyati

Mijozlarni qo‘llab-quvvatlash
Eng Ko‘p Ehtiyojingiz Bo‘lganda Yordam Oling
Avtomatlashtirish ehtiyojlaringiz uchun yordam berishga tayyormiz
Narxlar, mahsulot tafsilotlari yoki buyurtma bo‘yicha yordam uchun biz bilan bog‘laning — mutaxassislarimiz yordam berishga tayyor.
Qaytarish Huquqlaringizni Bilasizmi
Mahsulot sizning talablaringizga javob bermasa, uni qaytarish uchun 30 kun muddat bor. Toʻliq siyosat tafsilotlari uchun qarang.