{"product_id":"triconex-3664-digital-output-module-32-channel-24vdc-dual","title":"Triconex 3664 Digital Output Module - 32-Channel 24VDC Dual","description":"\u003ch2\u003e\u003cstrong\u003eTriconex 3664 Digital Output Module: Dual Redundant Safety Output\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eTriconex 3664\u003c\/strong\u003e Digital Output Module provides reliable dual-redundant control for safety-critical applications. This cost-optimized module from Triconex features \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003e32 output points\u003c\/strong\u003e\u003c\/span\u003e with advanced diagnostics and voting logic. The \u003cstrong\u003eTriconex 3664\u003c\/strong\u003e delivers robust performance for de-energize-to-trip control programs while maintaining essential safety redundancy.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eKey Technical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eThe \u003cstrong\u003eTriconex 3664\u003c\/strong\u003e provides \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003e32 commoned output points\u003c\/strong\u003e\u003c\/span\u003e for flexible system design\u003c\/li\u003e\n\u003cli\u003eIt operates at \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003e24 VDC nominal voltage\u003c\/strong\u003e\u003c\/span\u003e with wide operating range\u003c\/li\u003e\n\u003cli\u003eVoltage range spans from \u003cstrong\u003e16 to 30 VDC\u003c\/strong\u003e for reliable performance\u003c\/li\u003e\n\u003cli\u003eMaximum voltage rating is \u003cstrong\u003e36 VDC\u003c\/strong\u003e for robust operation\u003c\/li\u003e\n\u003cli\u003eTypical voltage drop remains \u003cstrong\u003eless than 1.5 VDC\u003c\/strong\u003e under load\u003c\/li\u003e\n\u003cli\u003eModule power load is \u003cstrong\u003eunder 10 watts\u003c\/strong\u003e for efficient operation\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eOutput Performance and Ratings\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eEach point handles \u003cstrong\u003e2A maximum continuous current\u003c\/strong\u003e for demanding loads\u003c\/li\u003e\n\u003cli\u003eSurge capability reaches \u003cstrong\u003e10A for 10 ms\u003c\/strong\u003e for inductive load switching\u003c\/li\u003e\n\u003cli\u003eLoad leakage is limited to \u003cstrong\u003e2 mA maximum\u003c\/strong\u003e for safety and efficiency\u003c\/li\u003e\n\u003cli\u003ePoint isolation provides \u003cstrong\u003e1500 VDC minimum\u003c\/strong\u003e protection\u003c\/li\u003e\n\u003cli\u003eThe module is \u003cstrong\u003eself-protecting\u003c\/strong\u003e and does not require external fuses\u003c\/li\u003e\n\u003cli\u003eDual serial architecture is \u003cstrong\u003eoptimized for de-energize-to-trip systems\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eAdvanced Diagnostics and Safety Features\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eVoltage loopback circuit \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003everifies each output switch operation\u003c\/strong\u003e\u003c\/span\u003e\n\u003c\/li\u003e\n\u003cli\u003eComprehensive diagnostics \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003econtinuously monitor all channels\u003c\/strong\u003e\u003c\/span\u003e\n\u003c\/li\u003e\n\u003cli\u003eModule status indicators show \u003cstrong\u003ePASS, FAULT, and ACTIVE\u003c\/strong\u003e states\u003c\/li\u003e\n\u003cli\u003eField alarm indicators detect \u003cstrong\u003eLOAD\/FUSE and output conditions\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003eIndividual \u003cstrong\u003eON\/OFF state indicators\u003c\/strong\u003e for each of the 32 output points\u003c\/li\u003e\n\u003cli\u003eStuck-ON and stuck-OFF fault detection \u003cstrong\u003eensures safe operation\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eDual Redundancy Architecture\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eDual circuitry provides \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003eessential redundancy for safety operations\u003c\/strong\u003e\u003c\/span\u003e\n\u003c\/li\u003e\n\u003cli\u003e2-out-of-3 voting process \u003cspan style=\"color: #ff6600;\"\u003e\u003cstrong\u003eensures reliable output signals\u003c\/strong\u003e\u003c\/span\u003e\n\u003c\/li\u003e\n\u003cli\u003eModule operates properly through \u003cstrong\u003emost single fault conditions\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003eHot-spare capability allows for \u003cstrong\u003eonline replacement of faulty modules\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003eMechanical keying prevents \u003cstrong\u003eimproper chassis installation\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003eRequires \u003cstrong\u003eexternal termination panel (ETP)\u003c\/strong\u003e with cable interface\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Integration\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eThe module is designed to \u003cstrong\u003esource current to field devices\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003eField power must be \u003cstrong\u003ewired to each output point\u003c\/strong\u003e on field termination\u003c\/li\u003e\n\u003cli\u003eDistinctive \u003cstrong\u003edark blue color code\u003c\/strong\u003e enables easy identification\u003c\/li\u003e\n\u003cli\u003eDesigned for \u003cstrong\u003ecost-sensitive safety applications\u003c\/strong\u003e where maximum availability is not critical\u003c\/li\u003e\n\u003cli\u003eIdeal for control programs where \u003cstrong\u003elow cost outweighs need for maximum availability\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003eSupports standard industrial \u003cstrong\u003e24 VDC control systems\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions (FAQ)\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eHow many output points does the 3664 module provide?\u003c\/strong\u003e\u003cbr\u003eThe \u003cstrong\u003eTriconex 3664\u003c\/strong\u003e delivers \u003cstrong\u003e32 digital output points\u003c\/strong\u003e with commoned configuration for flexible wiring\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWhat current can each output point handle?\u003c\/strong\u003e\u003cbr\u003eEach point supports \u003cstrong\u003e2A continuous current\u003c\/strong\u003e with \u003cstrong\u003e10A surge capability for 10ms\u003c\/strong\u003e for motor and solenoid loads\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDoes the module include diagnostic features?\u003c\/strong\u003e\u003cbr\u003eYes, the \u003cstrong\u003eTriconex 3664\u003c\/strong\u003e features comprehensive diagnostics including \u003cstrong\u003evoltage loopback testing and stuck output detection\u003c\/strong\u003e for safety assurance\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Triconex","offers":[{"title":"Default Title","offer_id":45286374965409,"sku":"3664","price":355.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0673\/5390\/3265\/files\/3664.jpg?v=1761807636","url":"https:\/\/www.autonexcontrol.com\/th\/products\/triconex-3664-digital-output-module-32-channel-24vdc-dual","provider":"AutoNex Controls Limited ","version":"1.0","type":"link"}