หน้าแรก
1756-A13 ControlLogix Chassis Allen-Bradley
1
/
จาก
3
1756-A13 ControlLogix Chassis Allen-Bradley
No reviews
มีสินค้าในสต็อก (20 ชิ้น) พร้อมจัดส่งแล้ว
-
ผู้ขาย:
Allen-Bradley
-
ประเภท:
ControlLogix Chassis
-
Country of Origin:
USA
-
Dimensions:
58.8*16.9*14.5cm
- Weight:
1900 g
- แท็ก: Controllogix chassis
Allen-Bradley 1756-A13 ControlLogix Chassis
Chassis Configuration & Layout
- Total Slot Capacity: 13 module slots for maximum flexibility
- Power Supply Location: Dedicated left-side slot (does not count toward 13 slots)
- Module Placement: Any ControlLogix module in any slot position
- Mounting Tabs: Eight secure mounting points for stable installation
- Slot Fillers: 1756-N2 modules required for all unused slots
Power Distribution System
- 5.1V DC Backplane: 15A chassis total / 6A per slot maximum
- 24V DC Backplane: 2.8A chassis total / 2.8A per slot maximum
- 3.3V DC Backplane: 4A chassis total / 4A per slot maximum
- 1.2V DC Backplane: 1.5A chassis total / 1.5A per slot maximum
- Power Dissipation: 5.4 Watts maximum under full load
Environmental Specifications
- Operating Temperature: 0°C to +60°C (+32°F to +140°F)
- Storage Temperature: -40°C to +85°C (-40°F to +185°F)
- Humidity Range: 5% to 95% relative humidity (non-condensing)
- Vibration Resistance: 2g @ 10-500 Hz during operation
- Shock Rating: 30g operational shock withstand capability
Electrical Installation Details
- Functional Earth Ground: 8.3 mm² (8 AWG) copper wire minimum
- Protective Earth Ground: 2.1 mm² (14 AWG) copper wire minimum
- Wire Temperature Rating: 90°C (194°F) or greater required
- Enclosure Type: Open-style for cabinet installation
- Wiring Access: Front-accessible terminal blocks
Frequently Asked Questions
What makes the 1756-A13 suitable for large systems?
- The 1756-A13 provides 13 expansion slots for comprehensive system configuration with multiple processors and specialized modules.
How does the backplane power distribution work?
- The chassis delivers 15A total at 5.1V DC, with each slot capable of drawing up to 6A for power-intensive modules.
What are the cabinet space requirements?
- You need minimum 30" W x 24" H x 8" D cabinet space for proper installation and maintenance access.
Can I mix different processor families?
- Yes, the chassis supports Logix 5560, 5570, and 5580 processors in any combination across slots.
What safety features are included?
- RIUP capability allows safe module replacement while powered, and electronic keying prevents installation errors.
How do I handle grounding requirements?
- Use 8 AWG for functional earth ground and 14 AWG for protective earth ground, both rated for 90°C or higher.
What maintenance is required?
- Regular inspection of connections, ensuring proper ventilation, and verifying ground integrity ensure long-term reliability.
For complete technical documentation and pricing, contact our automation specialists at: sales@nex-auto.com
จัดส่งรวดเร็วและเชื่อถือได้
จัดส่งทั่วโลกอย่างรวดเร็ว
ช่วยให้โครงการระบบอัตโนมัติของคุณเป็นไปตามกำหนดเวลา
แท้และเชื่อถือได้
ชิ้นส่วนทั้งหมดเป็นของแท้ 100%
เพื่อให้มั่นใจในประสิทธิภาพที่เชื่อถือได้สำหรับระบบของคุณ
- จัดส่งด่วน
- รับประกัน 12 เดือน
- คืนสินค้าได้ง่ายภายใน 30 วัน

ฝ่ายสนับสนุนลูกค้า
รับความช่วยเหลือเมื่อคุณต้องการมากที่สุด
พร้อมช่วยเหลือความต้องการด้านระบบอัตโนมัติของคุณ
ติดต่อเราเพื่อสอบถามราคาสินค้า รายละเอียดผลิตภัณฑ์ หรือขอความช่วยเหลือในการสั่งซื้อ — ผู้เชี่ยวชาญของเราพร้อมให้ความช่วยเหลือ
รู้สิทธิ์ในการคืนสินค้าของคุณ
คุณมีเวลา 30 วันในการคืนสินค้าหากสินค้าไม่ตรงตามความต้องการของคุณ ดูนโยบายฉบับเต็มสำหรับรายละเอียดเพิ่มเติม