{"product_id":"330101-00-65-10-02-05-bently-nevada-3300-xl-8mm-probe-1-0m","title":"330101-00-65-10-02-05 Bently Nevada 3300 XL 8mm Probe | 1.0m","description":"\u003ch2\u003e\u003cstrong\u003eKey Technical Specifications of 330101-00-65-10-02-05\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eBrand \u0026amp; Model:\u003c\/strong\u003e \u003cstrong\u003eBently Nevada\u003c\/strong\u003e \u003cstrong\u003e330101-00-65-10-02-05\u003c\/strong\u003e – \u003cspan style=\"color: #0066cc;\"\u003e3300 XL 8 mm Probe without armor\u003c\/span\u003e.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLinear Range:\u003c\/strong\u003e 2 mm (80 mils) starting from 0.25 mm (10 mils) off target. Range covers 0.25 mm to 2.3 mm (10 to 90 mils) outputting approx. –1 to –17 Vdc.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIncremental Scale Factor (ISF):\u003c\/strong\u003e \u003cspan style=\"color: #0066cc;\"\u003e7.87 V\/mm (200 mV\/mil) ±5%\u003c\/span\u003e for a 1 or 5 meter system. Includes interchangeability error from 0°C to +45°C.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eNominal Probe DC Resistance:\u003c\/strong\u003e RPROBE equals 7.59 ± 0.50 Ω for a 1.0 meter length (center conductor to outer conductor).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eExtension Cable Capacitance:\u003c\/strong\u003e 69.9 pF\/m (21.3 pF\/ft) typical value for reliable signal transmission.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eField Wiring Guidelines:\u003c\/strong\u003e Use 0.2 to 1.5 mm² (16 to 24 AWG) three-conductor shielded triad cable. Maximum length between Proximitor Sensor and monitor: \u003cspan style=\"color: #0066cc;\"\u003e305 meters (1000 feet)\u003c\/span\u003e.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDeviation from Best Fit Straight Line (DSL):\u003c\/strong\u003e Standard 1m system achieves less than ±0.025 mm (±1 mil) from 0°C to +45°C.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRecommended Gap for Radial Vibration:\u003c\/strong\u003e Set at -9 Vdc which corresponds to approximately 1.27 mm (50 mils).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProbe Tip Material:\u003c\/strong\u003e Polyphenylene sulfide (PPS) for rugged durability and coil encapsulation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProbe Case Material:\u003c\/strong\u003e AISI 303 or 304 stainless steel (SST) providing a robust mechanical structure.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight per Meter:\u003c\/strong\u003e 323 g\/m (11.4 oz) – lightweight yet strong assembly.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions (FAQ)\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Is this 330101-00-65-10-02-05 a genuine Bently Nevada probe?\u003c\/strong\u003e\u003cbr\u003eA: Yes, we supply brand new original Bently Nevada 3300 XL probes with full traceability.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: What is the linear range of this 3300 XL 8 mm probe?\u003c\/strong\u003e\u003cbr\u003eA: The linear range measures 2 mm (80 mils) starting at approximately 0.25 mm (10 mils) from the target.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Can I use this probe with an extension cable longer than 1 meter?\u003c\/strong\u003e\u003cbr\u003eA: Yes, Bently Nevada offers 5 and 9 meter system options. The scale factor tolerance changes to ±6.5% for longer systems.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: What torque should I apply when installing the probe?\u003c\/strong\u003e\u003cbr\u003eA: Bently Nevada recommends 11.2 N•m (100 in•lbf) for standard forward mounted probes. Do not exceed 33.9 N•m.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Does this probe withstand high temperature environments?\u003c\/strong\u003e\u003cbr\u003eA: The standard probe operates from -52°C to +177°C. Extended temperature range probes reach up to +218°C at the tip.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: What approvals does this model carry?\u003c\/strong\u003e\u003cbr\u003eA: Option 05 includes CSA, ATEX, and IECEx certifications for use in hazardous areas.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: Do you have stock available for 330101-00-65-10-02-05?\u003c\/strong\u003e\u003cbr\u003eA: Yes, we maintain inventory ready for immediate shipment.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eQ: What field wiring works best with the 3300 XL system?\u003c\/strong\u003e\u003cbr\u003eA: Use 0.2 to 1.5 mm² (16 to 24 AWG) three-conductor shielded triad cable. Maximum length is 305 meters to the monitor.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eContact Information Inquiries:\u003c\/strong\u003e Email \u003ca href=\"mailto:sales@nex-auto.com\"\u003esales@nex-auto.com\u003c\/a\u003e or call \u003ca href=\"https:\/\/wa.me\/8615392429628\"\u003e+86 153 9242 9628\u003c\/a\u003e (WhatsApp).\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003ePartner NexAuto Technology Limited:\u003c\/strong\u003e \u003ca href=\"https:\/\/www.nex-auto.com\/\"\u003ehttps:\/\/www.nex-auto.com\/\u003c\/a\u003e\u003c\/p\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":46422324969633,"sku":"330101-00-65-10-02-05","price":230.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0673\/5390\/3265\/files\/330101-00-65-10-02-05.jpg?v=1778488869","url":"https:\/\/www.autonexcontrol.com\/ru\/products\/330101-00-65-10-02-05-bently-nevada-3300-xl-8mm-probe-1-0m","provider":"AutoNex Controls Limited ","version":"1.0","type":"link"}