{"product_id":"330102-00-80-10-02-00-bently-nevada-8mm-probe","title":"330102-00-80-10-02-00 Bently Nevada - 8mm Probe","description":"\u003ch2\u003e\u003cstrong\u003eBently Nevada 330102-00-80-10-02-00 3300 XL 8 mm Proximity Probe\u003c\/strong\u003e\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eLinear Range:\u003c\/strong\u003e 2 mm (80 mils), starting at approximately 0.25 mm (10 mils) from target. Range extends from 0.25 to 2.3 mm (10 to 90 mils), corresponding to –1 to –17 Vdc output.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRecommended Gap (Radial Vibration):\u003c\/strong\u003e -9 Vdc, approximately 1.27 mm (50 mils). This setting ensures optimal performance for most radial vibration monitoring applications.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProbe DC Resistance (RPROBE):\u003c\/strong\u003e 7.59 ± 0.50 Ω for a 1.0 meter length. This value represents resistance from center conductor to outer conductor.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eField Wiring:\u003c\/strong\u003e Use 0.2 to 1.5 mm² (16 to 24 AWG) with 3-conductor shielded triad cable. Maximum cable length between the sensor and monitor is 305 meters (1,000 feet).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFrequency Response:\u003c\/strong\u003e Consult Figures 10 and 12 for signal roll-off at high frequencies when using longer field wiring lengths. The probe maintains accurate response within its specified range.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eOperating Environment \u0026amp; Approvals\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eTemperature Range (Standard Probe):\u003c\/strong\u003e -52°C to +177°C (-62°F to +350°F). Exposure below –34°C may reduce pressure seal life.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eExtended Temperature Option:\u003c\/strong\u003e Tip rated -52°C to +218°C (-62°F to +425°F); cable\/connector rated -51°C to +260°C (-60°F to +500°F).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRelative Humidity:\u003c\/strong\u003e Less than 3% change in Average Scale Factor (ASF) after 56 days at 93% humidity (IEC 68-2-3).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHazardous Area Approvals:\u003c\/strong\u003e Intrinsically safe (ia) for Class I, Zone 0 (AEx\/Ex ia IIC T5...T1 Ga) and Class I, Div 1, Groups A-G. Also nA\/ec for Class I, Zone 2 (AEx\/Ex nA IIC T5…T1 Gc) and Class I, Div 2, Groups A-D.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTemperature Schedules (Probe Only):\u003c\/strong\u003e T1 (-55°C to +232°C), T2 (-55°C to +177°C), T3 (-55°C to +120°C), T4 (-55°C to +80°C), T5 (-55°C to +40°C) for EPL Ga\/Gc. See full schedule for EPL Dc.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eMechanical \u0026amp; Installation Details\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eProbe Tip Material:\u003c\/strong\u003e Polyphenylene sulfide (PPS). Offers excellent chemical resistance and dimensional stability.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProbe Case Material:\u003c\/strong\u003e AISI 303 or 304 stainless steel (SST). Provides corrosion resistance and mechanical strength.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eThread Size:\u003c\/strong\u003e 3\/8-24 UNF. Maximum thread engagement length is 0.563 inches.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePressure Seal:\u003c\/strong\u003e Viton® O-ring seals differential pressure between tip and case. Probes are not pressure tested before shipment.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWeight:\u003c\/strong\u003e 323 g\/m (11.4 oz per meter). Lightweight design simplifies installation.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation \u0026amp; Packaging\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting:\u003c\/strong\u003e Ensure proper thread engagement (max 0.563 in). Use recommended torque values for the 3\/8-24 UNF thread.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCable Routing:\u003c\/strong\u003e Avoid sharp bends and protect the coaxial ClickLoc connector. Standard cable length is 1.0 meter (3.3 feet).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePackage Contents:\u003c\/strong\u003e 1 × \u003cstrong\u003e330102-00-80-10-02-00\u003c\/strong\u003e probe with attached cable and ClickLoc connector. No additional accessories included.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShipping Options:\u003c\/strong\u003e We ship via FedEx, UPS, and DHL. Delivery typically within 5 business days after order confirmation.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions (FAQ)\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eIs this a new, original Bently Nevada probe?\u003c\/strong\u003e Yes, we supply brand new, original \u003cstrong\u003e3300 XL\u003c\/strong\u003e probes directly from authorized sources.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWhat is the lead time for this product?\u003c\/strong\u003e We maintain stock and ship within 5 business days via DHL, FedEx, or UPS.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCan I return the probe if it doesn't fit my application?\u003c\/strong\u003e We accept returns within 30 days of delivery, provided the probe is unused and in original packaging.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWhat is the maximum cable extension for this sensor?\u003c\/strong\u003e You can extend field wiring up to 305 meters (1,000 feet) between the \u003cstrong\u003e3300 XL\u003c\/strong\u003e Proximitor and monitor.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDoes the probe work in high-humidity environments?\u003c\/strong\u003e Yes, it shows less than 3% ASF change after 56 days at 93% relative humidity per IEC 68-2-3.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIs the probe intrinsically safe?\u003c\/strong\u003e Yes, it carries ia certification for Class I, Zone 0 and nA\/ec for Zone 2 when installed per approved drawings.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp style=\"margin-top: 20px;\"\u003e\u003cstrong\u003eContact Information:\u003c\/strong\u003e For inquiries, please email \u003ca href=\"mailto:sales@nex-auto.com\"\u003esales@nex-auto.com\u003c\/a\u003e or call \u003ca href=\"https:\/\/wa.me\/861539249628?text=Inquiry%20about%20Bently%20Nevada%20330102-00-80-10-02-00\" rel=\"noopener\" target=\"_blank\"\u003e+86 153 9242 9628\u003c\/a\u003e (WhatsApp).\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003ePartner:\u003c\/strong\u003e \u003ca href=\"https:\/\/www.nex-auto.com\/\" rel=\"noopener\" target=\"_blank\"\u003eNexAuto Technology Limited\u003c\/a\u003e\u003c\/p\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":46929054597281,"sku":"330102-00-80-10-02-00","price":224.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0673\/5390\/3265\/files\/330102-00-80-10-02-00-2.jpg?v=1787733199","url":"https:\/\/www.autonexcontrol.com\/products\/330102-00-80-10-02-00-bently-nevada-8mm-probe","provider":"AutoNex Controls Limited ","version":"1.0","type":"link"}