Home
Allen-Bradley 1756-OC8 DC Output Module
1
/
di
3
Allen-Bradley 1756-OC8 DC Output Module
No reviews
Disponibile (23 unità), pronto per essere spedito
-
Venditore:
Allen-Bradley
-
Tipo:
DC Output Module
-
Country of Origin:
USA
-
Dimensions:
15*10*4cm
- Weight:
500 g
- Tag: Dc output module
Allen-Bradley 1756-OC8 ControlLogix Digital Output Module
Core Technical Specifications
- Brand & Manufacturer: Allen Bradley
- Series: ControlLogix
- Model Number: 1756-OC8
- Module Type: DC Output Module
- Rated Voltage: 48 Volts DC Source
- Operating Voltage Range: 30-60 Volts DC
- Output Points: 8 Points (4 points per group)
- Max Current per Point: 2 Amps at 60°C
- Max Current per Module: 8 Amps at 60°C
Electrical & Performance Data
- Surge Current: 4 Amps for 10 ms per point (repeatable)
- On-State Voltage Drop: 2 VDC maximum at 2A
- Off-State Leakage: 1 mA maximum per point
- Output Delay: 1 ms (Off to On), 2 ms (On to Off)
- Minimum Load Current: 2 mA
- Backplane Power: 0.89 Watts
- Current Draw: 165 mA @ 5.1V, 2 mA @ 24V
Installation & Compatibility
- Required Terminal Block: 20-pin 1756-TBNH or 1756-TBSH (sold separately).
- Mounting: Install in any slot of a grounded ControlLogix chassis.
- Protection Note: Module is not fused; use a fused IFM (Input/Output Module) for output protection.
- Recommended Fuse: 5x20mm 4A quick-acting fuse (e.g., SOC MQ2-4A).
- Isolation Voltage: 50 Volts continuous.
Operational & System Features
- Communication Formats: Rack Optimization, Scheduled Output Data, Listen-Only modes.
- Fault State Configuration: Set per point to On, Off, or Hold Last State (default is Off).
- Power Dissipation: 4.9 Watts maximum at 60°C.
- Thermal Dissipation: 16.71 BTU/hour.
- Operating Temperature: Rated for up to 60°C (140°F).
Frequently Asked Questions (FAQ)
-
Q: What voltage does the 1756-OC8 module require?
A: The 1756-OC8 operates on a 30-60V DC supply, with a nominal rating of 48V DC. -
Q: How much current can I draw from a single output?
A: Each output point supports a maximum continuous current of 2 Amps at 60°C. -
Q: What terminal block do I need for this module?
A: You need a 20-pin removable terminal block, either the 1756-TBNH or the 1756-TBSH. -
Q: Is fuse protection included with the module?
A: No, the module is not internally fused. We recommend using an external fused IFM for protection. A 4A quick-acting fuse is suggested. -
Q: Do you have the 1756-OC8 in stock ready to ship?
A: Yes, we stock the 1756-OC8 and typically ship orders within 5 business days.
For more information or to purchase the 1756-OC8 module, contact our sales team today.
Contact Information Inquiries: sales@nex-auto.com , +86 153 9242 9628
Partner NexAuto Technology Limited : https://www.nex-auto.com/
Spedizione Veloce e Affidabile
Consegna rapida in tutto il mondo
mantiene i tuoi progetti di automazione nei tempi previsti.
Autentico e Affidabile
Tutti i componenti sono 100% autentici
garantendo prestazioni affidabili per i tuoi sistemi.
- Consegna Espressa
- 12 Mesi di Garanzia
- Reso facile entro 30 giorni

Assistenza Clienti
Ricevi aiuto quando ne hai più bisogno
Qui per assisterti con le tue esigenze di automazione
Contattaci per prezzi, dettagli sul prodotto o assistenza per l'ordine — i nostri esperti sono disponibili per aiutarti.
Conosci i tuoi diritti di reso
Hai 30 giorni per restituire un prodotto se non soddisfa le tue esigenze. Consulta la politica completa per i dettagli.