Allen‑Bradley 1791-0A32 High‑Density AC Output Block I/O
Key Technical Specifications
- Output channels: 32 (four groups of eight), 20‑132 VAC, 47‑63 Hz.
- Minimum on‑state current: 50 mA per output; maximum continuous 300 mA at 60 °C (vertical).
- Surge current: 10 A for 50 ms, repeatable every two seconds (1200 W inrush).
- Output delay: OFF→ON 1.0 ms; ON→OFF 8.3 ms (60 Hz) / 10 ms (50 Hz).
- Isolation & protection: Internal power supply with protection circuitry; group‑to‑group isolation ensures reliable operation.
- External power required: 85‑132 VAC, 47‑63 Hz; supplies both logic and outputs.
- Off‑state leakage: 3 mA max; voltage drop 1.5 V peak at 300 mA.
Installation, Mounting, and Wiring
- Mount the 1791-0A32 vertically or horizontally. Vertical mounting allows 600 mA per output at 30 °C, derating to 300 mA at 60 °C.
- Horizontal orientation supports 300 mA at 30 °C and 150 mA at 60 °C.
- Power connects to terminals L1 (1), N (3), and GND (2); RIO wiring uses BLU (6), CLR (8), and SHD (7) on the left side.
- Open the front cover to set the I/O rack number via the group switch assembly. Status LEDs on the cover aid troubleshooting.
- Operate the module between 0 °C and 60 °C. Use appropriate conductors (e.g., 14 AWG) for field terminations.
Frequently Asked Questions
-
What is the output voltage range of the 1791‑OA32?
It accepts 20‑132 VAC, 47‑63 Hz; nominal 120 VAC. External control power must be 85‑132 VAC. -
How many output groups does it have, and are they isolated?
The 1791‑OA32 has four groups of eight outputs each. Groups are isolated from one another for reliable operation. -
Which controllers work with this module?
It is compatible with PLC‑2, PLC‑3, and PLC‑5 families via RIO scanners such as 1771‑SN, 1772‑SD, 1775‑S5, and PLC‑5 VME (6008‑LTV). -
How does mounting orientation affect output current?
Vertical mounting provides higher capacity (600 mA at 30 °C). Horizontal reduces it (300 mA at 30 °C) – always respect derating at elevated temperatures. -
What do the status LEDs indicate?
Front‑panel LEDs show power, communication, and output status, simplifying troubleshooting. -
Do you offer same‑day shipping?
We dispatch within five days via FedEx, UPS, or DHL. Stock is available.
For further assistance, contact our sales team: sales@nex-auto.com or +86 153 9242 9628 (WhatsApp).
Partner with NexAuto Technology Limited: https://www.nex-auto.com/
Expédition rapide et fiable
Livraison rapide dans le monde entier
pour que vos projets d'automatisation respectent les délais.
Authentique et Fiable
Tous les composants sont 100 % authentiques
garantissant des performances fiables pour vos systèmes.
- Livraison express
- 12 mois de garantie
- Retour facile sous 30 jours

Service client
Obtenez de l'aide quand vous en avez le plus besoin
Ici pour répondre à vos besoins en automatisation
Contactez-nous pour les tarifs, les détails du produit ou l'assistance à la commande — nos experts sont disponibles pour vous aider.
Connaissez vos droits de retour
Vous disposez de 30 jours pour retourner un produit s’il ne répond pas à vos attentes. Consultez la politique complète pour plus de détails.